• Be sure to lay the drain hose downward for
smooth drainflow.
1
2
1
No trap allowed
2
Not to rise
• Be careful not to allow the drain hose to
rise, form a trap or leave its end in water,
as shown below.
1
2
3
1
Not running wavy
2
No trap allowed
3
Not left in water
• Coil thermal insulation around a drain hose
extension, if running in the room.
• It is recommended to add an "intermediate
air vent" when the drain hose is extended
horizontally, or an "anti-back-flow air vent"
when the hose is exposed to high winds
on a high-rise building, for example. For
this purpose, employ a "T tube joint" (PVC-
made, commercially available) halfway in
the hose.
2
1
1
To drainage pit
2
Air vent (T tube joint)
Connecting the refrigerant pipes
• Use pipes with thickness 0.8mm.
• Connect the pipes for the indoor unit first
and then for the outdoor unit.
• Bend the pipes carefully as not to damage
them.
• Do not over tighten the tubes; it may be
deformed or damaged.
Use a torque wrench, when possible. See
the table below for the flare nut tightening
torque.
Flare nut tightening torque
Tube size
Torque
Liquid side
1/4"
16±2N·m (1.6±0.2kgf·m)
Gas side
3/8"
38±4N·m (3.8±0.4kgf·m)
Flaring the pipe end
1. Cutting with a pipe cutter
Cut at a right angle.
2. Deburring
Allow no cuttings in the pipe.
3. Putting in the flare nut
4. Flaring
Flare processing dimensions (A) differ ac-
cording to the type of flare tool.
electrolux
9
Summary of Contents for EXH09HX
Page 67: ...electrolux 67 ...