The optimum drying performances are achieved when the measured static back pressure correspond to the value
listed in the following table.
Heating
Effect
Hz
Optimum static back pressure — measured at
position A (Pa) in a cold empty machine
Resulting: Nominal air flow in a cold empty ma-
chine (m
3
/h)
Electric
18.0 kW
50
580
580
Electric
18.0 kW
60
885
580
Gas
21.0 kW
50
570
690
Gas
21.0 kW
60
900
670
Steam
25.0 kW
50
570
690
Steam
25.0 kW
60
900
670
Diagram with pressure drop curve
The grey area (A) illustrates the optimal working area.
A
Working area
B
Optimum airflow cold empty machine
C
Counter pressure, Pa
D
Air flow m
3
/h
0
100
200
300
400
500
600
700
800
900
1000
1100
0
100
200
300
400
500
600
700
800
900
1000
1100
1200
C
D
TD6-20 ,GAS/STEAM ,21/25kW ,400V/3/50Hz
A
B
fig.X01548
0
100
200
300
400
500
600
700
800
900
1000
1100
1200
1300
1400
0
100
200
300
400
500
600
700
800
900
1000
C
D
TD6-20 ,GAS/STEAM ,21/25kW ,400V/3/60Hz
A
B
fig.X01549