6: Ethernet Configuration
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
6.3.4: Setup Details
This section illustrates how each section of settings appears on the screen, if you
press Y (Yes) to change one or more of the settings.
CAUTION! Change Settings 1 and 6 ONLY. Settings 2, 3, and 4 must be the same as
shown in Section 6.2.1. If they are not, reset them to the values shown in Section
6.2.1.
Network IP Settings Detail (1) (Set device with static IP Address.)
Network Mode: 0=Wired only, 1=Wireless Only <0> ? 1
IP Address <010> 192.<000> 168.<000> .<000> .<001>
Set Gateway IP Address <N> ? Y
Gateway IP Address : <192> .<168> .<000> .<001>
Set Netmask <N for default> <Y> ? Y
<255> .<255> .<255> .<000>
Change telnet config password <N> ? N
Serial & Mode Settings (2) (Make sure these settings match those shown in
Section 6.2.1.)
Attached Device (1=Slave 2=Master) (1) ? 1
Serial Protocol (1=Modbus/RTU 2=Modbus/ASCII) (1) ? 1
Use serial connector (1=CH1 2=CH2) (1) ? 1
Interface Type (1=RS232 2=RS422/RS485+4-wire 3=RS485+2-wire) (1) ? 1
Enter serial parameters (57600,8,N,1) 57600, 8, N, 1