![Electro Industries Shark 100S Installation & Operation Manual Download Page 131](http://html.mh-extra.com/html/electro-industries/shark-100s/shark-100s_installation-and-operation-manual_2379713131.webp)
B: Modbus Map
Doc# E145721 MM-1
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Description
1
Format
Range
6
Units or
Resolution
Comments
#
Reg
read-only
0000 - 0007
1 - 8
Meter Name
ASCII
16 char
none
8
0008 - 000F
9 - 16
Meter Serial Number
ASCII
16 char
none
8
0010 - 0010
17 - 17
Meter Ty
p
e
UINT16
bit-ma
pp
ed
-------t -----vvv
t = transducer model (1=yes, 0=no),
vvv = V-switch(1 to 4)
1
0011 - 0012
18 - 19
Firmware Version
ASCII
4 char
none
2
0013 - 0013
20 - 20
Ma
p
Version
UINT16
0 to 65535
none
1
0014 - 0014
21 - 21
Meter Configuration
UINT16
bit-ma
pp
ed
-------- --ffffff
ffffff = calibration frequency (50 or 60)
1
0015 - 0015
22 - 22
ASIC Version
UINT16
0-65535
none
1
0016 - 0026
23 - 39
Reserved
17
0027 - 002E
40 - 47
Reserved
8
Block Size:
47
read-only
0383 - 0384
900 - 901
Watts, 3-Ph total
FLOAT
-9999 M to +9999 M
watts
2
0385 - 0386
902 - 903
VARs, 3-Ph total
FLOAT
-9999 M to +9999 M
VARs
2
0387 - 0388
904 - 905
VAs, 3-Ph total
FLOAT
-9999 M to +9999 M
VAs
2
Block Size:
6
read-only
03E7 - 03E8
1000 - 1001
Volts A-N
FLOAT
0 to 9999 M
volts
2
03E9 - 03EA
1002 - 1003
Volts B-N
FLOAT
0 to 9999 M
volts
2
03EB - 03EC
1004 - 1005
Volts C-N
FLOAT
0 to 9999 M
volts
2
03ED - 03EE
1006 - 1007
Volts A-B
FLOAT
0 to 9999 M
volts
2
03EF - 03F0
1008 - 1009
Volts B-C
FLOAT
0 to 9999 M
volts
2
03F1 - 03F2
1010 - 1011
Volts C-A
FLOAT
0 to 9999 M
volts
2
03F3 - 03F4
1012 - 1013
Am
p
s A
FLOAT
0 to 9999 M
am
p
s
2
03F5 - 03F6
1014 - 1015
Am
p
s B
FLOAT
0 to 9999 M
am
p
s
2
03F7 - 03F8
1016 - 1017
Am
p
s C
FLOAT
0 to 9999 M
am
p
s
2
03F9 - 03FA
1018 - 1019
Watts, 3-Ph total
FLOAT
-9999 M to +9999 M
watts
2
03FB - 03FC
1020 - 1021
VARs, 3-Ph total
FLOAT
-9999 M to +9999 M
VARs
2
03FD - 03FE
1022 - 1023
VAs, 3-Ph total
FLOAT
-9999 M to +9999 M
VAs
2
03FF - 0400
1024 - 1025
Power Factor, 3-Ph total
FLOAT
-1.00 to +1.00
none
2
0401 - 0402
1026 - 1027
Frequency
FLOAT
0 to 65.00
Hz
2
0403 - 0404
1028 - 1029
Neutral Current
FLOAT
0 to 9999 M
am
p
s
2
Block Size:
30
Identification Block
Meter Data Section
2
Primary Readings Block, 60 cycles (IEEE Floating Point)
Modbus Address
Fixed Data Section
Hex
Decimal
Primary Readings Block, 6 cycles (IEEE Floating Point)
Summary of Contents for Shark 100S