![Electro Industries Shark 100S Installation & Operation Manual Download Page 142](http://html.mh-extra.com/html/electro-industries/shark-100s/shark-100s_installation-and-operation-manual_2379713142.webp)
C: DNP Map
Doc# E145721 DNP-2
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Object
Point
Var
Description
Format
Range
Multiplier
Units
Comments
30
10
5 Watts, 3-Ph total
SINT16
-32768 to +32767
(4500 / 32768)
W
30
11
5 VARs, 3-Ph total
SINT16
-32768 to +32767
(4500 / 32768)
VAR
30
12
5 VAs, 3-Ph total
SINT16
0 to +32767
(4500 / 32768)
VA
30
13
5 Power Factor, 3-Ph total
SINT16
-1000 to +1000
0.001
none
30
14
5 Frequency
SINT16
0 to 9999
0.01
Hz
30
15
5 Positive Watts, 3-Ph,
Maximum Avg Demand
SINT16
-32768 to +32767
(4500 / 32768)
W
30
16
5 Positive VARs, 3-Ph,
Maximum Avg Demand
SINT16
-32768 to +32767
(4500 / 32768)
VAR
30
17
5 Negative Watts, 3-Ph,
Maximum Avg Demand
SINT16
-32768 to +32767
(4500 / 32768)
W
30
18
5 Negative VARs, 3-Ph,
Maximum Avg Demand
SINT16
-32768 to +32767
(4500 / 32768)
VAR
30
19
5 VAs, 3-Ph, Maximum Avg
Demand
SINT16
-32768 to +32767
(4500 / 32768)
VA
30
20
5 Angle, Phase A Current
SINT16
-1800 to +1800
0.1
degree
30
21
5 Angle, Phase B Current
SINT16
-1800 to +1800
0.1
degree
30
22
5 Angle, Phase C Current
SINT16
-1800 to +1800
0.1
degree
30
23
5 Angle, Volts A-B
SINT16
-1800 to +1800
0.1
degree
30
24
5 Angle, Volts B-C
SINT16
-1800 to +1800
0.1
degree
30
25
5 Angle, Volts C-A
SINT16
-1800 to +1800
0.1
degree
30
26
5 CT numerator
SINT16
1 to 9999
N/A
none
CT ratio =
30
27
5 CT multi
p
lier
SINT16
1, 10, or 100
N/A
none
(numerator * multi
p
lier) / denominator
30
28
5 CT denominator
SINT16
1 or 5
N/A
none
30
29
5 PT numerator
SINT16
1 to 9999
N/A
none
PT ratio =
30
30
5 PT multi
p
lier
SINT16
1, 10, or 100
N/A
none
(numerator * multi
p
lier) / denominator
30
31
5 PT denominator
SINT16
1 to 9999
N/A
none
30
32
5 Neutral Current
SINT16
0 to 32767
(10 / 32768)
A
For 1A model, multi
p
lier is (2 / 32768) and
values above 2A secondary read 32767.
80
0
1 Device Restart Bit
N/A
N/A
N/A
none
Clear via Function 2 (Write), Qualifier Code
0.
Internal Indication
Electro Industries/GaugeTech
Summary of Contents for Shark 100S