![Electro Industries/GaugeTech Shark 100 Quick Start Manual Download Page 3](http://html.mh-extra.com/html/electro-industries-gaugetech/shark-100/shark-100_quick-start-manual_2379735003.webp)
Doc
#
E145703 V.1.14
QS - 3
Shark® 100 Meter Quickstart
Electro
Industries/GaugeTech
™
Powered by Innovation™
Program Settings Using the Faceplate Buttons:
(MENU, ENTER, DOWN ARROW, RIGHT ARROW)
See the figure on the right for the location of the
faceplate buttons.
Access Configuration Mode:
1.Push the
MENU
button - you will see
the display on the right; rSt will be
blinking.
2.Press the
DOWN ARROW
once.
CFG (Configuration) moves to the
top of the display.
3.Press the
ENTER
button. You will
see the Configuration menu, shown
on the right.
4.Press the
DOWN ARROW
and then press the
ENTER
button. You will see the CT
numerator setting screen (Ct-n). The current CT numerator is shown in the second
line. To change the setting, press the
DOWN
ARROW
until the value you want is
displayed. Then press the
RIGHT ARROW
to move to the next digit. Repeat until
the setting is done.
5.Press the
ENTER
button to go to the CT denominator screen (CT-d). This setting is
display only - it can’t be changed.
6.Press the
ENTER
button to go to the CT Scaling setting screen (CT-S). The current
Scaling is shown in the second line. Press the
DOWN ARROW
to choose another
value. You can choose 1, 10, or 100.
7.Press the
ENTER
button to go to the PT numerator setting screen (Pt-n).The current
PT numerator is shown in the second line. To change the setting, press the
DOWN
ARROW
until the value you want is displayed. Then press the
RIGHT ARROW
to
move to the next digit. Repeat until the setting is done.
8.Press the
ENTER
button to go to the PT-denominator screen (Pt-d). The current
PT denominator is shown in the second line. To change the setting, press the
DOWN
ARROW
until the value you want is displayed. Then press the
RIGHT ARROW
to
move to the next digit. Repeat until the setting is done.
9.Press the
ENTER
button to go to the PT Scaling setting screen (PT-S). The current
Scaling is shown in the second line. Press the
DOWN ARROW
to choose another
value. You can choose 1, 10, 100, or 1000.
NOTE:
See example CT and PT settings on page QS-5.
0.659
0000
-
-
-
A
B
C
MENU
ENTER
MAX
MIN
LM1
LM2
%THD
PRG
VOLTS L-N
VOLTS L-L
AMPS
W/VAR/PF
VA/Hz
lrDA
Wh
VARh
VAh
120%-
90%-
60%-
30%-
%LOAD
MEGA
KILO
Wh Pulse
A
B
C
-
-
-
MENU
ENTER
A
B
C
-
-
-
MENU
ENTER
A
B
C
-
-
-
MENU
ENTER
A
B
C
-
-
-
MENU
ENTER
A
B
C
-
-
-
MENU
ENTER
A
B
C
-
-
-
MENU
ENTER
A
B
C
-
-
-
MENU
ENTER