EDA-D6000 Installation Manual 

 

Page 1 of 6                                      Ref: EDA_D6000_Install_V107.doc    

 

 

 

 

             

 

Electro-Detectors

 

Zerio Plus

 

EDA-D6000 Radio Combined Heat Detector and Sounder 

Installation Instructions 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
The  EDA-D6000  Radio  Combined  Heat  Detector  and  Sounder  is  used  as  part  of  the  Zerio  Plus  Radio  Fire  Alarm 
System.  It cannot be used with other ranges of Electro-Detectors products. 
 
The unit is rated to IP21C and should only be used for indoor use. 
 

To fix the base to the ceiling 

The  heat  detector  should  be  fitted  in  an  appropriate  position  as  detailed  in  BS5839  Part  1.  The  base  plate  should  be 
separated from the unit by rotating the detector anti-clockwise and pulling apart. The base should be screwed to a flat 
surface  using  2  x  No  6  screws  of  appropriate  length  for  the  material  that  the  unit  is  being  mounted  on.  It  is 
recommended  that  the  base  should  be  used  as  a  template  for  the  screw  holes.  If  the  surface  is  not  flat,  the  unit  may 
buckle  and  cause  tamper  conditions,  when  screwed  tightly  to  the  surface.  It  is  recommended  that  the  units  not  be 
secured too tightly or a rigid mounting plate be fixed to the wall first. The units should not be fitted covering holes in 
ceilings  where  water  could  possibly drip through. Any hole should be made good prior to installing the detector. The 
unit should be fitted away from any metal objects or electrical items to avoid radio interference and a radio survey for 
the position should have been carried out prior to installation.  
 

Adding the device to the system 

Before the unit will operate on a system, it must be programmed via the control panel.  To program the unit the panel 
must be set in the appropriate mode to add a device to the system. If a device is being added or replaced on the system 
then the appropriate menu option should be selected on the control panel. Please refer to the panel manual for further 
information.  Before adding/replacing the device on the system you will need to know what unit number/address the unit 
is  to  be  programmed  to.    The  zone  number,  sensitivity,  volume,  area  and  text  location  information  should  also  be  to 
hand but this can be added/changed later. Some of this information is left at default. 
 

 

 

       

  

 

        0359 

 

Electro Detectors Ltd. 

Electro House 

Edinburgh Way 

Harlow, Essex 

CM20 2EG, UK

 

EN54-3:2001+A1:2002+A2:2006 
EN54-5:2000+A1:2002 
EN54-25:2008 
 
0359-CPR-00228 (2014) 
DOP_EDA_D6000 

 
EDA-D6000

  

Radio combined heat detector 
and sounder for use in fire 
detection and fire alarm systems 
for buildings. 
Type:   A1S 

A-for in-door use. 

 

www.acornfiresecurity.com

www.acornfiresecurity.com

Summary of Contents for Zerio Plus EDA-D6000

Page 1: ... where water could possibly drip through Any hole should be made good prior to installing the detector The unit should be fitted away from any metal objects or electrical items to avoid radio interference and a radio survey for the position should have been carried out prior to installation Adding the device to the system Before the unit will operate on a system it must be programmed via the contr...

Page 2: ...sitivity 0 5 1 0 and 2o C per minute The unit will also operate once 54o C has been exceeded Alarm Verify The time period in seconds that a detector remains in alarm before sending an alarm signal Range 1 to 20 seconds The recommended value which conforms with third party type approval tests is 2 Seconds Volume The volume of the unit when it is sounding can be set inside the unit We would recommen...

Page 3: ... setting When programming the panel for each device that can set the system into alarm a set of cause and effects can be programmed to determine how the sounders operate The options are detailed below The system defaults to sounder tone number 0 and has been type approved to this Other options have not been approved Four user defined tones can be added to the system The swept tone sweeps from 1056...

Page 4: ...ned with the led on the outer case The detector should be located in the base and rotated clockwise Once mounted correctly press the reset button for about a second until it beeps The LED should stop flashing if the unit is mounted correctly Should the temperature exceed the alarm condition threshold the unit will indicate the alarm condition by illuminating the LED The internal buzzer on the dete...

Page 5: ...pproaching their end of life The unit will continue to operate for a further 60 days in which time the batteries should be changed Verify Fail The panel has lost communication with the device this could be caused by the batteries being flat the unit failing to operate something obstructing the radio signal path or the device not being installed correctly with an adequate signal strength Battery Fa...

Page 6: ...EDA D6000 Installation Manual Page 6 of 6 Ref EDA_D6000_Install_V107 doc Electro Detectors Polar Diagram for swept tone at maximum volume www acornfiresecurity com www acornfiresecurity com ...

Reviews: