background image

 

EDA-D6000 Installation Manual 

 

Page 5 of 6                                      Ref: EDA_D6000_Install_V107.doc    

 

 

 

 

             

 

Electro-Detectors

 

 
1.

 

Remove the detector from the base by rotating the detector anti-clockwise and separating the unit. 

2.

 

Remove the power link. 

3.

 

Remove the back plate by removing the two screws 

4.

 

Remove the old battery pack. 

5.

 

Fit the new battery pack making sure the battery’s pins are lined up and pressed down. 

6.

 

Re-fit the back plate. 

7.

 

Press and hold the unit removal and reset button simultaneously. 

8.

 

With these buttons pressed down, fit the power link. 

9.

 

Let the unit go into its log-on mode, (it will beep) and keep the buttons pressed down. 

10.

 

After another 5 seconds a second BEEP will sound, at this point release the buttons.  This will re-set the battery 
counter after a further 15 minutes. If you realise that you didn’t want to reset the counter, then power the unit 
down by removing the power pin. Leave for 5 seconds and re-apply the power. The counter will not reset. 

11.

 

Refit the device onto its base. 

 

 
Faults displayed on the control panel from heat detectors:- 

 

Low  Battery: 

The  batteries  are  approaching  their  end  of  life.    The  unit  will  continue  to  operate  for  a  further  60 

days in which time the batteries should be changed. 
 

Verify Fail: 

The panel has lost communication with the device, this could be caused by the batteries being flat, the 

unit failing to operate, something obstructing the radio signal path or the device not being installed correctly with an 
adequate signal strength. 
 

Battery Fault:

 The unit has detected a problem with the battery. 

 

Unit Removal: 

If the unit is removed from its base, the panel will display a unit removal/tamper fault. 

 

Tx/Rx Fault: 

A failure with the transmit / receive module of the device. It is suggested that the fault should be reset 

and if the same fault occurs within 60 minutes the unit be replaced. 
 

Int Fault:

 The unit has detected an internal problem with the way it is operating. There are several faults that can 

cause this but the usual way of solving the problem is to replace the unit or return it for repair. It is suggested that 
the fault should be reset and if the same fault occurs within 60 minutes the unit be replaced. The faults can relate to 
the  operation  of  the  sensing  head,  if  fitted,  the  micro-processor  controlling  the  device,  its  internal  memory  and  a 
host more. 
 

www.acornfiresecurity.com

www.acornfiresecurity.com

Summary of Contents for Zerio Plus EDA-D6000

Page 1: ... where water could possibly drip through Any hole should be made good prior to installing the detector The unit should be fitted away from any metal objects or electrical items to avoid radio interference and a radio survey for the position should have been carried out prior to installation Adding the device to the system Before the unit will operate on a system it must be programmed via the contr...

Page 2: ...sitivity 0 5 1 0 and 2o C per minute The unit will also operate once 54o C has been exceeded Alarm Verify The time period in seconds that a detector remains in alarm before sending an alarm signal Range 1 to 20 seconds The recommended value which conforms with third party type approval tests is 2 Seconds Volume The volume of the unit when it is sounding can be set inside the unit We would recommen...

Page 3: ... setting When programming the panel for each device that can set the system into alarm a set of cause and effects can be programmed to determine how the sounders operate The options are detailed below The system defaults to sounder tone number 0 and has been type approved to this Other options have not been approved Four user defined tones can be added to the system The swept tone sweeps from 1056...

Page 4: ...ned with the led on the outer case The detector should be located in the base and rotated clockwise Once mounted correctly press the reset button for about a second until it beeps The LED should stop flashing if the unit is mounted correctly Should the temperature exceed the alarm condition threshold the unit will indicate the alarm condition by illuminating the LED The internal buzzer on the dete...

Page 5: ...pproaching their end of life The unit will continue to operate for a further 60 days in which time the batteries should be changed Verify Fail The panel has lost communication with the device this could be caused by the batteries being flat the unit failing to operate something obstructing the radio signal path or the device not being installed correctly with an adequate signal strength Battery Fa...

Page 6: ...EDA D6000 Installation Manual Page 6 of 6 Ref EDA_D6000_Install_V107 doc Electro Detectors Polar Diagram for swept tone at maximum volume www acornfiresecurity com www acornfiresecurity com ...

Reviews: