![Electra LEX 12 Service Manual Download Page 26](http://html1.mh-extra.com/html/electra/lex-12/lex-12_service-manual_2378857026.webp)
5-13
PERFORMANCE DATA & PRESSURE CURVES
Revision Y06-01
Service Manual - LEX
5.10
LEX14 / ONG14 R410A
5.10.1
Cooling Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
LEGEND
TC –
Total Cooling Capacity, kW
SC – Sensible
Capacity,
kW
PI –
Power Input, kW
WB – Wet Bulb Temp., (
o
C)
DB –
Dry Bulb Temp., (
o
C)
ID
–
Indoor
OD –
Outdoor
(1) Marked area is below standard operating limits. For operating in low ambient
conditions, refer to Optional Accessories (Chapter 15).
Entering Air WB/DB ID Coil(
o
C)
15/21
17/24
19/27
21/29
23/32
TC
4.45
4.61
4.72
4.83
4.90
15
(1)
SC
2.89
3.01
3.13
3.21
3.27
PI
0.93
0.93
0.93
0.93
0.94
TC
4.30
4.54
4.68
4.79
4.89
20
(1)
SC
2.83
2.98
3.11
3.20
3.26
PI
1.01
1.01
1.02
1.02
1.02
TC
4.07
4.40
4.62
4.76
4.88
25
SC
2.76
2.93
3.09
3.18
3.23
PI
1.09
1.10
1.10
1.11
1.12
TC
3.81
4.15
4.48
4.64
4.78
30
SC
2.67
2.84
3.02
3.11
3.17
PI
1.18
1.19
1.20
1.21
1.22
TC
3.53
3.83
4.22
4.43
4.64
35
SC
2.54
2.72
2.95
3.04
3.09
PI
1.27
1.29
1.31
1.32
1.33
TC
3.21
3.49
3.81
4.16
4.38
40
SC
2.39
2.58
2.79
2.88
2.94
PI
1.37
1.39
1.41
1.43
1.44
TC
2.78
3.04
3.34
3.69
3.98
46
SC
2.21
2.36
2.54
2.63
2.69
PI
1.49
1.52
1.55
1.57
1.59
Entering Air DB
OD Coil(
o
C)
Data