5-10
PERFORMANCE DATA & PRESSURE CURVES
Revision Y06-01
Service Manual - LEX
5.7.2
Heating Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
*
the above chart includes the weighted deicing infleuence.
LEGEND
TH –
Total Heating Capacity, kW
PI
– Power Input, kW
WB –
Wet Bulb Temp., (
o
C)
DB –
Dry Bulb Temp., (
o
C)
ID
–
Indoor
OD –
Outdoor
5.8
Capacity Correction Factor Due to Tubing Length
5.8.1 Cooling
TOTAL TUBING LENGTH (One Way)
3m
7.5m
10m
15m
20m
25m
30m
40m
50m
1.02
1
0.961
0.948
---
---
---
---
---
*
Minimum recommended tubing length between indoor and outdoor units is 3m.
5.8.2 Heating
TOTAL TUBING LENGTH (One Way)
3m
7.5m
10m
15m
20m
25m
30m
40m
50m
1.05
1
0.975
0.963
---
---
---
---
---
*
Minimum recommended tubing length between indoor and outdoor units is 3m.
15
20
25
ENTERING WB
OD COIL(
o
C)
TH
Pl
TH
Pl
TH
Pl
-10
2.18
0.92
2.10
0.98
2.01
1.02
-7
2.34
0.94
2.26
0.99
2.18
1.04
-2
2.49
0.95
2.41
1.01
2.32
1.06
2
3.03
1.00
2.91
1.06
2.78
1.12
6
4.27
1.07
4.15
1.15
4.00
1.22
10
4.65
1.13
4.52
1.21
4.40
1.29
15
5.02
1.18
4.90
1.27
4.77
1.35
20
5.29
1.21
5.17
1.32
5.02
1.42
ENTERING AIR DB ID COIL(
O
C)