TROUBLE SHOOTING
Version - 1 52 JKD DCI
11.2.4 Open circuit or short circuit of temperature sensor diagnosis and solution (E5)
Error Code
E4/E5/F1/F2/F3
Malfunction decision
conditions
If the sampling voltage is lower than 0.06V or higher than 4.94V,
the LED will display the failure.
Supposed causes
●
Wiring mistake
●
Sensor faulty
●
PCB faulty
Trouble shooting:
Check the connection
between temperature
sensor and PCB.
Correct the connection
No
Yes
Replace indoor or outdoor
main PCB
Measure the resistance
value of the sensor
Repalce the sensor
No
Yes
Summary of Contents for ELAU-VKD009-H11
Page 12: ...DIMENSIONS Version 1 12 JKD DCI For ELSI JKD009 N11 For ELSI JKD012 N11...
Page 13: ...DIMENSION JKD DCI 13 Version 1 For ELSI JKD018 N11 For ELSI JKD024 N11...
Page 16: ...DIMENSIONS Version 1 16 JKD DCI...
Page 28: ...WIRING DIAGRAM Version 1 28 JKD DCI 7 3 Outdoor unit ELAU VKD018 H11...
Page 29: ...WIRING DIAGRAM JKD DCI 29 Version 1 7 4 Outdoor unit ELAU VKD024 H11...
Page 66: ...EXPLODED VIEW AND SPARE PART LIST Version 1 66 JKD DCI 12 2 ELSI JKD012 N11...
Page 68: ...EXPLODED VIEW AND SPARE PART LIST Version 1 68 JKD DCI 12 3 ELSI JKD018 N11...
Page 70: ...EXPLODED VIEW AND SPARE PART LIST Version 1 70 JKD DCI 12 4 ELSI JKD024 N11...
Page 72: ...EXPLODED VIEW AND SPARE PART LIST Version 1 72 JKD DCI 12 5 ELAU VKD009 H11...
Page 74: ...EXPLODED VIEW AND SPARE PART LIST Version 1 74 JKD DCI 12 6 ELAU VKD012 H11...
Page 76: ...EXPLODED VIEW AND SPARE PART LIST Version 1 76 JKD DCI 12 7 ELAU VKD018 H11...
Page 78: ...EXPLODED VIEW AND SPARE PART LIST Version 1 78 JKD DCI 12 8 ELAU VKD024 H11...
Page 80: ...SERVICE MANUAL JKD DCI Series...