8.3 Pipe length and the elevation
The pipe length and refrigerant amount:
Model
Pipe size
Standard
length
(m)
Max.
Elevation
B (m)
Max.
Length
A (m)
Additional
refrigerant
(g/m)
Gas
Liquid
MS12FU-09HRFN1-QRD0GW(B) +
MOBA31-09HFN1-QRDOGW
3/8’’
(
Ф9.52)
1/4’’
(Ф6.35)
5
10
25
15
MS12FU-12HRFN1-QRD0GW(B) +
MOB31-12HFN1-QRD0GW
3/8’’
(
Ф9.52)
1/4’’
(Ф6.35)
5
10
25
15
MS12FU-18HRFN1-QRD0GW(B) +
MOB31-18HFN1-QRD0GW
1/2
’’
(Ф12.7)
1/4’’
(Ф6.35)
5
20
30
15
MS12FU-24HRFN1-
MOCA30-24HFN1-QRD0GW
5/
8’’
(
Ф15.9)
3/8’’
(
Ф9.52)
5
25
50
30
Caution:
The capacity test is based on the standard length and the maximum permissive length is based on the
system reliability.
Summary of Contents for ELAU-VKD009-H11
Page 12: ...DIMENSIONS Version 1 12 JKD DCI For ELSI JKD009 N11 For ELSI JKD012 N11...
Page 13: ...DIMENSION JKD DCI 13 Version 1 For ELSI JKD018 N11 For ELSI JKD024 N11...
Page 16: ...DIMENSIONS Version 1 16 JKD DCI...
Page 28: ...WIRING DIAGRAM Version 1 28 JKD DCI 7 3 Outdoor unit ELAU VKD018 H11...
Page 29: ...WIRING DIAGRAM JKD DCI 29 Version 1 7 4 Outdoor unit ELAU VKD024 H11...
Page 66: ...EXPLODED VIEW AND SPARE PART LIST Version 1 66 JKD DCI 12 2 ELSI JKD012 N11...
Page 68: ...EXPLODED VIEW AND SPARE PART LIST Version 1 68 JKD DCI 12 3 ELSI JKD018 N11...
Page 70: ...EXPLODED VIEW AND SPARE PART LIST Version 1 70 JKD DCI 12 4 ELSI JKD024 N11...
Page 72: ...EXPLODED VIEW AND SPARE PART LIST Version 1 72 JKD DCI 12 5 ELAU VKD009 H11...
Page 74: ...EXPLODED VIEW AND SPARE PART LIST Version 1 74 JKD DCI 12 6 ELAU VKD012 H11...
Page 76: ...EXPLODED VIEW AND SPARE PART LIST Version 1 76 JKD DCI 12 7 ELAU VKD018 H11...
Page 78: ...EXPLODED VIEW AND SPARE PART LIST Version 1 78 JKD DCI 12 8 ELAU VKD024 H11...
Page 80: ...SERVICE MANUAL JKD DCI Series...