INSTALLATION DETAILS
Version - 1 30 JKD DCI
8. Installation Details
8.1 Wrench torque sheet for installation
Outside diameter
Torque
Additional tightening torque
mm
inch
N.cm
N.cm
Ф6.35
1/4
1500(153kgf.cm)
1600(163kgf.cm)
Ф9.52
3/8
2500(255kgf.cm)
2600(265kgf.cm)
Ф12.7
1/2
3500(357kgf.cm)
3600(367kgf.cm)
Ф15.9
5/8
4500(459kgf.cm)
4700(479kgf.cm)
Ф19
3/4
6500(663kgf.cm)
6700(683kgf.cm)
8.2 Connecting the cables
The power cord of connect should be selected according to the following specifications sheet.
Rated current of appliance
Nominal cross-sectional area (mm²)
>3 and ≤6
0.75
>6 and ≤10
1
>10 and ≤16
1.5
>16 and ≤25
2.5
The cable size and the current of the fuse or switch are determined by the maximum current indicated
on the nameplate which located on the side panel of the unit. Please refer to the nameplate before
selecting the cable, fuse and switch.
Summary of Contents for ELAU-VKD009-H11
Page 12: ...DIMENSIONS Version 1 12 JKD DCI For ELSI JKD009 N11 For ELSI JKD012 N11...
Page 13: ...DIMENSION JKD DCI 13 Version 1 For ELSI JKD018 N11 For ELSI JKD024 N11...
Page 16: ...DIMENSIONS Version 1 16 JKD DCI...
Page 28: ...WIRING DIAGRAM Version 1 28 JKD DCI 7 3 Outdoor unit ELAU VKD018 H11...
Page 29: ...WIRING DIAGRAM JKD DCI 29 Version 1 7 4 Outdoor unit ELAU VKD024 H11...
Page 66: ...EXPLODED VIEW AND SPARE PART LIST Version 1 66 JKD DCI 12 2 ELSI JKD012 N11...
Page 68: ...EXPLODED VIEW AND SPARE PART LIST Version 1 68 JKD DCI 12 3 ELSI JKD018 N11...
Page 70: ...EXPLODED VIEW AND SPARE PART LIST Version 1 70 JKD DCI 12 4 ELSI JKD024 N11...
Page 72: ...EXPLODED VIEW AND SPARE PART LIST Version 1 72 JKD DCI 12 5 ELAU VKD009 H11...
Page 74: ...EXPLODED VIEW AND SPARE PART LIST Version 1 74 JKD DCI 12 6 ELAU VKD012 H11...
Page 76: ...EXPLODED VIEW AND SPARE PART LIST Version 1 76 JKD DCI 12 7 ELAU VKD018 H11...
Page 78: ...EXPLODED VIEW AND SPARE PART LIST Version 1 78 JKD DCI 12 8 ELAU VKD024 H11...
Page 80: ...SERVICE MANUAL JKD DCI Series...