TROUBLESHOOTING
Service Manual – VBZ DCI 1-A.1 GB
13-5
2. Poor heat exchange of Heatsink
3. PFC reactor problem.
4. Abnormal power voltage
5. PFC circuit problem on PCB
Desynchronizing of compressor
H7
7
1. Abnormal power input voltage.
2. Compressor
wiring
mistake.
3. Liquid and gas valve are not open.
4. EEV damaged or not proper working
5. Poor heat exchange.
6. Over charged system.
。
Compressor start-up failure
Lc
11
1. Compressor
wiring
mistake
2. Over charged system
3. System not balanced before compressor
starting
4. Compressor
problem
Compressor phase current
detection problem
U1
12
Phase current detection circuit for compressor
has problem.
DC over current
P5
15
1. Abnormal power input voltage.
2. Compressor
wiring
mistake.
3. Liquid and gas valve are not open.
4. EEV damaged or not proper working
5. Poor heat exchange.
6. Over charged system.
Charging malfunction of
capacitor
PU
17
1. Reactor
open
2. Charging relay or other components
damaged on PCB.
HST failure
P7
18
1. Senor was broken or damaged
2. PCB temperature detection circuit has
problem
HST over heating protection
P8
19
1. Insufficient attachment of IPM module to
Heatsink
2. Outdoor PCB problem.
DC under voltage
PL
21
1. AC input voltage is too low
2. Reactor has problem
3. ODU PCB has problem
Lack Phase Protection of
Compressor
Ld
1. Compressor
wiring
problem
2. Compressor
problem
3. IPM module problem or compressor
current detection circuit has problem
4. Compressor malfunction due to EEV
problem
13.1.5
Checking the refrigeration system
Checking system pressures and other thermodynamic measures should be done when system
is in Test Mode (in Test mode, system operates in fixed settings). The performance curves
given in this manual are given for unit performance in test mode when high indoor fan speed is
selected.
Entering test mode please refer to section 12- Control system.
13.2
Simple procedures for checking the Main Parts
13.2.1
Checking Mains Voltage.
Confirm that the Mains voltage is between 198 and 264 VAC. If Mains voltage is out of this
range, abnormal operation of the system is expected. If in range check the Power (Circuit)
Breaker and look for broken or loosed cable lugs or wiring mistake(s).
13.2.2 Checking
Power
Input.
Summary of Contents for ELAU-VBZ214-H11
Page 16: ...OUTLINE DIMENSION 4 2 Service Manual VBZ DCI 1 A 1 GB 4 2 Indoor JYD018...
Page 17: ...OUTLINE DIMENSION 4 3 Outdoor VBZ214 Service Manual VBZ DCI 1 A 1 GB 4 3...
Page 18: ...OUTLINE DIMENSION 4 4 Service Manual VBZ DCI 1 A 1 GB 4 4 Outdoor VBZ318 VBZ430...
Page 35: ...WIRING DIAGRAM 9 2 Service Manual VBZ DCI 1 A 1 GB 9 3 YAZ214...
Page 36: ...WIRING DIAGRAM 9 4 YAZ318 Service Manual VBZ DCI 1 A 1 GB 9 3...
Page 37: ...WIRING DIAGRAM 9 4 Service Manual VBZ DCI 1 A 1 GB 9 5 YAZ430...
Page 38: ...WIRING DIAGRAM 9 6 Wiring connection between IDU and ODU Service Manual VBZ DCI 1 A 1 GB 9 5...
Page 39: ...WIRING DIAGRAM 10 REFRIGERATION DIAGRAMS Service Manual VBZ DCI 1 A 1 GB 10 1...
Page 73: ...EXPLODED VIEW SPARE PART LIST 15 12 Service Manual VBZ DCI 1 A 1 GB APPENDIX...