CONTROL SYSTEM
Service Manual – VBZ DCI 1-A.1 GB
12-9
12.8.4 Compressor
over Heating Protection
The Discharging temperature is used as the compressor’s internal temperature. If the discharge
temperature rises above a certain level, the operating frequency upper limit is set to keep this
temperature from going up further.
Compressor frequency will be reduced when CTT reaches above 97C
Compressor will stop when CTT reaches 110C
If the unit stops as such protection for 6 times
(the counter will be cleared after the compressor has
run for 7min)
, it can not resume running automatically and display malfunction, it can resume by
power reset.
12.8.5
Compressor over Current Protection
Detect an input current by the CT during the compressor is running, and set the frequency upper
limit from such input current. In case of heat pump model, this control is the upper limit control
function of the frequency which takes priority of the lower limit of four way valve activating
compensation.
Detail
For model 14: Compressor will stop when AC current >= 16.0A for continuously 2.5s
For model 18/30: Compressor will stop when AC current >= 20.0A for continuously 2.5s
If the unit stops as such protection for 6 times (the counter will be cleared after the compressor has
run for 7min), it can not resume running automatically and display malfunction, it can resume by
power reset.
12.8.6
Outdoor Coil Deicing Protection
This protection is for Heat Pump Only
This protection is carried out by the cooling cycle (reverse cycle). The defrosting time or outdoor
heat exchanger temperature must be more than its setting values when finishing the deicing
protection.
In the deicing protection, IFAN is forced OFF.
12.8.6.1 Deicing Starting Conditions
The starting conditions must be made with the outdoor air temperature (OAT) and outdoor coil
temperature (OCT). Under the conditions that the system is in heating operation, after the time for
defrosting is judged to be satisfied, if the temperature for deicing is satisfied after detections for
continuous 1 minute, the deicing operation will start.
Summary of Contents for ELAU-VBZ214-H11
Page 16: ...OUTLINE DIMENSION 4 2 Service Manual VBZ DCI 1 A 1 GB 4 2 Indoor JYD018...
Page 17: ...OUTLINE DIMENSION 4 3 Outdoor VBZ214 Service Manual VBZ DCI 1 A 1 GB 4 3...
Page 18: ...OUTLINE DIMENSION 4 4 Service Manual VBZ DCI 1 A 1 GB 4 4 Outdoor VBZ318 VBZ430...
Page 35: ...WIRING DIAGRAM 9 2 Service Manual VBZ DCI 1 A 1 GB 9 3 YAZ214...
Page 36: ...WIRING DIAGRAM 9 4 YAZ318 Service Manual VBZ DCI 1 A 1 GB 9 3...
Page 37: ...WIRING DIAGRAM 9 4 Service Manual VBZ DCI 1 A 1 GB 9 5 YAZ430...
Page 38: ...WIRING DIAGRAM 9 6 Wiring connection between IDU and ODU Service Manual VBZ DCI 1 A 1 GB 9 5...
Page 39: ...WIRING DIAGRAM 10 REFRIGERATION DIAGRAMS Service Manual VBZ DCI 1 A 1 GB 10 1...
Page 73: ...EXPLODED VIEW SPARE PART LIST 15 12 Service Manual VBZ DCI 1 A 1 GB APPENDIX...