PERFROMANCE
DATA
5-6
Service Manual – VBZ DCI 1-A.1 GB
5.3.3
Heating Capacity (kW)
ID COIL ENTERING AIR DB TEMPERATURE [C
0
]
OD COIL
ENTERING AIR
DB/WB
TEMPERATURE
[C
0
] DATA 15
20
25
TC 4.63
4.35
4.06
-15/-16
PI 1.54
1.76
1.98
TC 5.55
5.27
4.98
-10/-12
PI 1.77
1.99
2.21
TC 6.24
5.95
5.67
-7/-8
PI 1.94
2.17
2.39
TC 6.59
6.30
6.01
-1/-2
PI 2.03
2.25
2.47
TC 6.82
6.53
6.24
2/1
PI 2.09
2.31
2.53
TC 8.99
8.70
8.41
7/6
PI 2.18
2.40
2.62
TC 9.34
9.06
8.77
10/9
PI 2.28
2.50
2.72
TC 9.70
9.42
9.13
15/12
PI 2.38
2.60
2.82
15-24
TC
85 - 105 % of nominal
(Protection Range)
PI
80 - 120 % of nominal
LEGEND
TH – Total Heating Capacity, kW
PI
– Power Input, kW
WB –
Wet Bulb Temp., (
o
C)
DB – Dry Bulb Temp., (
o
C)
ID – Indoor
OU –
Outdoor
5.3.4 Capacity
Correction
Factors
Heating Capacity Ratio Vs. Outdoor Temperature
0.5
0.6
0.7
0.8
0.9
1
1.1
1.2
-15
-10
-5
0
5
10
15
Outdoor WB Temperature [deg C]
Ca
p
a
c
it
y
Ra
ti
o
n
Summary of Contents for ELAU-VBZ214-H11
Page 16: ...OUTLINE DIMENSION 4 2 Service Manual VBZ DCI 1 A 1 GB 4 2 Indoor JYD018...
Page 17: ...OUTLINE DIMENSION 4 3 Outdoor VBZ214 Service Manual VBZ DCI 1 A 1 GB 4 3...
Page 18: ...OUTLINE DIMENSION 4 4 Service Manual VBZ DCI 1 A 1 GB 4 4 Outdoor VBZ318 VBZ430...
Page 35: ...WIRING DIAGRAM 9 2 Service Manual VBZ DCI 1 A 1 GB 9 3 YAZ214...
Page 36: ...WIRING DIAGRAM 9 4 YAZ318 Service Manual VBZ DCI 1 A 1 GB 9 3...
Page 37: ...WIRING DIAGRAM 9 4 Service Manual VBZ DCI 1 A 1 GB 9 5 YAZ430...
Page 38: ...WIRING DIAGRAM 9 6 Wiring connection between IDU and ODU Service Manual VBZ DCI 1 A 1 GB 9 5...
Page 39: ...WIRING DIAGRAM 10 REFRIGERATION DIAGRAMS Service Manual VBZ DCI 1 A 1 GB 10 1...
Page 73: ...EXPLODED VIEW SPARE PART LIST 15 12 Service Manual VBZ DCI 1 A 1 GB APPENDIX...