![Electra CN 25 DCI Service Manual Download Page 9](http://html.mh-extra.com/html/electra/cn-25-dci/cn-25-dci_service-manual_2378827009.webp)
2-3
PRODUCT DATA SHEET
SM CN 1-E.1 GB
2.3
CN 50 DCI R410A
Model Indoor Unit
CN-50 DCI
Model Outdoor Unit
DCI 50 R410A
Installation Method of Pipe
Flared
Characteristics
Units
Cooling Heating
Capacity
(4)
Btu/hr
17050(4450-20500)
19100(4450-23900)
kW
5.0(1.3-6.0)
5.6(1.3-7.0)
Power input
(4)
kW
1.56(0.46-2.11)
1.55(0.36-2.50)
EER (Cooling) or COP(Heating)
(4)
W/W
3.22 3.62
Energy efficiency class
A
A
Power supply
V/Ph/Hz
220-240V/Single/50Hz
Rated current
A
7.0
7.2
Starting current
A
10.5
Circuit breaker rating
A
20
INDOOR
Fan type & quantity
Centrifugal x 1
Fan speeds
H/M/L
RPM
750/650/550
750/650/550
Air flow
(1)
H/M/L
m3/hr
700
700
External static pressure
Min-Max
Pa
0
Sound power level
(2)
H/M/L
dB(A)
53
53
Sound pressure level
(3)
H/M/L
dB(A)
38/30
38/30
Moisture removal
l/hr
2.07
Condenstate drain tube I.D
mm
20
Dimensions
WxHxD
mm
575*575*270
Weight
kg
???
PaCNage dimensions
WxHxD
mm
575X575X270
PaCNaged weight
kg
15.2
Units per pallet
units
681X681X348
StaCNing height
units
17.7
OUTDOOR
Refrigerant control
Electronical Expansion Valve
Compressor type,model
Single Rotary DC Inverter,Panasonic 5RS130XCC03
Fan type & quantity
Propeller x 1
Fan speeds
H/L
RPM
920
Air flow
H/L
m3/hr
2160
Sound power level
H/L
dB(A)
62
63
Sound pressure level
(3)
H/L
dB(A)
52
53
Dimensions
WxHxD
mm
795*290*610
Weight
kg
39
PaCNage dimensions
WxHxD
mm
945*395*655
PaCNaged weight
kg
43
Units per pallet
Units
9
StaCNing height
units
3 levels
Refrigerant type
R410A
Refrigerant chargless distance
kg/m
1.5kg/7.5m
Additional charge
g/m
No need
Connections
between units
Liquid line
In.(mm)
1/4"(6.35)
Suction line
In.(mm)
1/2"(12.7)
Max.tubing length
m.
Max.30
Max.height difference
m.
Max.10
Operation control type
Remote control
Heating elements
kW
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511.
(2) Airflow in ducted units; at nominal external static pressure.
(3) Sound power in ducted units is measured at air discharge.
(4) Sound pressure level measured at 1 meter distance from unit.
CONTENT
Summary of Contents for CN 25 DCI
Page 15: ...4 2 OUTLINE DIMENSIONS SM CN 1 E 1 GB 4 2 Outdoor Unit DCI 50 4 3 Outdoor Unit DCI 60 CONTENT ...
Page 16: ...4 3 OUTLINE DIMENSIONS SM CN 1 E 1 GB 4 4 Outdoor Unit DCI 72Z CONTENT ...
Page 44: ...8 1 WIRING DIAGRAMS SM CN 1 E 1 GB 8 WIRING DIAGRAMS 8 1 CN 25 35 50 60 70 DCI CONTENT ...
Page 92: ...13 12 EXPLODED VIEWS AND SPARE PARTS LISTS SM CN 1 E 1 GB 13 11 Outdoor Unit DCI 60 CONTENT ...
Page 94: ...13 14 EXPLODED VIEWS AND SPARE PARTS LISTS SM CN 1 E 1 GB 13 13 Outdoor Unit DCI 72Z CONTENT ...