![Electra CN 25 DCI Service Manual Download Page 25](http://html.mh-extra.com/html/electra/cn-25-dci/cn-25-dci_service-manual_2378827025.webp)
5-9
PERFORMANCE DATA & PRESSURE CURVES
SM CN 1-E.1 GB
5.3 CN
50
DCI
5.3.1
Cooling Capacity (kW) - Run Mode
[230V] : Indoor Fan at High Speed.
ID COIL ENTERING AIR DB/WB TEMPERATURE [C
0
]
OD COIL
ENTERING AIR DB
TEMPERATURE [
0
C]
DATA
22/15
24/17
27/19
29/21
32/23
-10 - 20
(protection range)
TC
80 - 110 % of nominal
SC
80 - 105 % of nominal
PI
25 - 50 % of nominal
25
TC
4.83
5.15
5.47
5.78
6.10
SC
3.43
3.50
3.57
3.64
3.71
PI
1.23
1.25
1.27
1.30
1.32
30
TC
4.60
4.92
5.23
5.55
5.86
SC
3.35
3.42
3.49
3.56
3.63
PI
1.37
1.39
1.42
1.44
1.46
35
TC
4.37
4.68
5.00
5.32
5.63
SC
3.26
3.33
3.40
3.47
3.54
PI
1.51
1.54
1.56
1.58
1.61
40
TC
4.14
4.45
4.77
5.08
5.40
SC
3.17
3.24
3.31
3.38
3.45
PI
1.66
1.68
1.70
1.73
1.75
46
TC
3.86
4.17
4.49
4.80
5.12
SC
3.07
3.14
3.21
3.28
3.35
PI
1.83
1.85
1.88
1.90
1.92
LEGEND
TC –
Total Cooling Capacity, kW
SC – Sensible
Capacity,
kW
PI –
Power Input, kW
WB – Wet Bulb Temp., (
o
C)
DB –
Dry Bulb Temp., (
o
C)
ID
–
Indoor
OU –
Outdoor
5.3.2 Capacity
Correction
Factors
Cooling Capacity Ratio Vs. Outdoor Temperature
0.50
0.60
0.70
0.80
0.90
1.00
1.10
1.20
20
25
30
35
40
45
Outdoor Temperature [ºC]
Cap
aci
ty
Rat
io
CONTENT
Summary of Contents for CN 25 DCI
Page 15: ...4 2 OUTLINE DIMENSIONS SM CN 1 E 1 GB 4 2 Outdoor Unit DCI 50 4 3 Outdoor Unit DCI 60 CONTENT ...
Page 16: ...4 3 OUTLINE DIMENSIONS SM CN 1 E 1 GB 4 4 Outdoor Unit DCI 72Z CONTENT ...
Page 44: ...8 1 WIRING DIAGRAMS SM CN 1 E 1 GB 8 WIRING DIAGRAMS 8 1 CN 25 35 50 60 70 DCI CONTENT ...
Page 92: ...13 12 EXPLODED VIEWS AND SPARE PARTS LISTS SM CN 1 E 1 GB 13 11 Outdoor Unit DCI 60 CONTENT ...
Page 94: ...13 14 EXPLODED VIEWS AND SPARE PARTS LISTS SM CN 1 E 1 GB 13 13 Outdoor Unit DCI 72Z CONTENT ...