![Electra CN 25 DCI Service Manual Download Page 63](http://html.mh-extra.com/html/electra/cn-25-dci/cn-25-dci_service-manual_2378827063.webp)
11-16
CONTROL SYSTEM
SM CN 1-E.1 GB
● Presence Detector/Power Shedding Selection
Select the functions of dry contact PD/PS by setting the Dip switch J9
Selection
J9
Presence Detector
OFF
Power Shedding
ON
● Installation of height compensation settings (By installer)
The compensation settings according to installation height should be set by using the dip switch J12,
J13 on the controller PCB
Installation Height
J12
J13
Installation height
H0
OFF
OFF
2.1-2.7m
H1(Factory setting)
ON
OFF
2.7-3.3m
H2
OFF
ON
>3.3m
H3
ON
ON
Reserved
Compensation data according to the installation height
Installation
Height
Speed Compensation for
Heating Mode
Speed Compensation for
other Modes
Temperature compensation
in heating mode
CN
CN
CN
CN
CN
CN
H0
-50
0
-50
0
4
2
H1
0
150
0
150
4
2
H2
100
150
100
150
6
2
H3
150
150
150
150
7
2
CONTENT
Summary of Contents for CN 25 DCI
Page 15: ...4 2 OUTLINE DIMENSIONS SM CN 1 E 1 GB 4 2 Outdoor Unit DCI 50 4 3 Outdoor Unit DCI 60 CONTENT ...
Page 16: ...4 3 OUTLINE DIMENSIONS SM CN 1 E 1 GB 4 4 Outdoor Unit DCI 72Z CONTENT ...
Page 44: ...8 1 WIRING DIAGRAMS SM CN 1 E 1 GB 8 WIRING DIAGRAMS 8 1 CN 25 35 50 60 70 DCI CONTENT ...
Page 92: ...13 12 EXPLODED VIEWS AND SPARE PARTS LISTS SM CN 1 E 1 GB 13 11 Outdoor Unit DCI 60 CONTENT ...
Page 94: ...13 14 EXPLODED VIEWS AND SPARE PARTS LISTS SM CN 1 E 1 GB 13 13 Outdoor Unit DCI 72Z CONTENT ...