ELCOS SRL
- Parma - CEM-120 – PROG – EN
9
PROGRAMMABLE TIMES
DESCRIPTION
SECONDS
ADJUSTMENT
RANGE
FACTORY
SETTING
PREHEATING TIME
preheating operation time.
0 to 60
0 (off)
STARTING TIME
operation time of attempt to start.
5 to 25
5
PAUSE TIME
pause between attempts to start.
1 to 20
5
STOPPING TIME
Stopping system operation time after the engine running signal has disappeared.
1 to 55
20
COOLING TIME
Engine operating time between the moment of releasing the generator contactor and
operation of the stopping system.
0 to 360
120
START-UP DELAY AFTER THE CALL
With the call contact closed and the delay expired, start-up begins.
1 to 600
1
STOP DELAY AFTER OPENING OF THE CALL
On opening of the call contact and after the delay has expired, the generator contactor is
de-energized.
1 to 600
1
TIME FOR CONNECTION OF THE GENERAL ALARM
Number 350 indicates continuous operation with no time limits.
10 to 350
350
(continuous
operation)
WEEKLY SELF-TEST DURATION
When the test time expires, the engine stops.
1 to 60
minutes
3 minutes
INSUFFICIENT INTERVENTION TIME OR PUMP WATER OVERPRESSURE
after the
increase or lowering of pump water pressure and when this time has expired, the stopping
process begins.
0 to 300
5
PREHEATING
TIME
STARTING
TIME
PAUSE
TIME
STOPPING
TIME
0 s
5 s
5 s
20 s
0 s
5 s
5 s
20 s
PREHEATING TIME.
Preheating operation time. 0 seconds, preheating off.
STARTING TIME.
Operation time in the attempt to start.
PAUSE TIME.
Pause between attempts to start.
STOPPING TIME.
Stopping system time after the engine running signal has disappeared.
Press to change the time
Press to change the time
Press to change the time
Press to change the time
Time
Time
Time
Time
Decreases
Decreases
Decreases
Decreases
Increases
Increases
Increases
Increases
Press and wait for
the system to write
PROGRAMMED
.
Press and wait for
the system to write
PROGRAMMED.
Press and wait for
the system to write
PROGRAMMED.
Press and wait for
the system to write
PROGRAMMED.
Press to
display.
Press to
display.
Press to
display.
Press to
display.