ELCOS SRL
- Parma - CEM-120 – PROG – EN
13
Factory
setting
NORMAL
OPERATION
REVERSED
OPERATION
NORMAL
OPERATION
NORMAL
OPERATION
REVERSED
OPERATION
CHOICE OF RADIATOR FLUID LEVEL PROBE.
DESCRIPTION
CHOICE OF PROBES
CHOICE
OF PROBES
CHARGING ALTERN.
ANOMALY
NUMBER OF STARTUP
ATTEMPTS
OIL PRESSURE LOW
WARNING
START WITH
FLAT BATTERY
RADIATOR
LEVEL PROBE
NO
FUEL
95°C
NO STOP
NO STOP
100°C
PROGRAM ONE LEVEL AT A TIME
ENGINE OVERTEMPERATURE WARNING.
CHARGING ALTERNATOR FAULT. It is possible to program the stop; by factory default it is programmed to stop.
NUMBER OF ATTEMPTS TO START. 10 attempts to start can be programmed. (Failure to start).
LOW OIL PRESSURE WARNING. (The pressure measured by the pressure transmitter). This is programmed as notification and does
not stop the engine. (The low pressure detected by the pressure switch causes the engine to stop).
STARTING OF GENERATOR SET WITH BATTERY WITH LOW CHARGE. (With control unit in automatic mode). Starts or stops the
generator set depending on the voltage measured at the battery terminals.
FUEL RESERVE.
Does not stop the engine.
FUEL FINISHED
. It is possible to program the stop; by factory default it is programmed to stop.
OVERTEMPERATURE.
Press when the arrow is
next to the parameter to be modified
Press when the arrow is
next to the parameter to be modified
Press when the arrow is
next to the parameter to be modified.
Press when the arrow is
next to the parameter to be modified
Press when the arrow is
next to the parameter to be modified
Press to choose.
Press when the arrow is
next to the parameter to be modified
Press when the arrow is
next to the parameter to be modified
Press and wait for
the system to write
PROGRAMMED.
THIS IS
DISPLAYED
ON THE DISPLAY
THIS IS
DISPLAYED
ON THE DISPLAY
Press to
display.
Stop
of engine
Delay
in intervention
Delay
in intervention
Delay
in intervention
Stop
of engine
Stop
of engine
Decreases
Number
of attempts
Increases
INTERVENTION DUE TO ENGINE OVERTEMPERATURE. The temperature is measured by the (TEMPERATURE) TRANSMITTER and is
programmable. The protection device can be set on two levels and intervenes when these are exceeded. The warning level is
programmed only as notification, the other level is programmed to stop the engine (the overtemperature is also detected by the
thermostat that always causes the engine to stop).
Threshold
Threshold
Minimum threshold
Maximum threshold
Threshold
Threshold
STOP
RADIATOR
CORE
IN THE ABSENCE OF
LIQUID,
REMOVES
THE
GROUND SIGNAL
THE CONTROL UNIT IS
PROGRAMMED FOR
NORMAL OPERATION
RADIATOR
CORE
IN THE ABSENCE
OF LIQUID,
ACTIVATES
THE
GROUND SIGNAL
• FUEL
RESERVE (10%)
• FUEL
FINISHED (1%)
95°C/203°F
NO STOP
100°C/212°F
1%
3 s.STOP
0.5Bar/500Kpa
1 s
12.4Volt
13.6
1200 s
12.4Volt 13.6
1200 s
0.5Bar
1 s
1%
3 s STOP
Press to
display.
Press to
display.
Press to
display.
Press to
display.
Press to
display.
Press to
display.
Press and wait for
the system to write
PROGRAMMED.
Press and wait for
the system to write
PROGRAMMED.
Press and wait for
the system to write
PROGRAMMED.
Press and wait for
the system to write
PROGRAMMED.
Press and wait for
the system to write
PROGRAMMED.
Press and wait for
the system to write
PROGRAMMED.
Press and wait for
the system to write
PROGRAMMED.
Press to
display.
OVERHEATING
WARNING
OVERHEATING
ENGINE
4