ELCOS CEM-120 Technical Programming Operations Manual Download Page 13

 ELCOS SRL 

- Parma - CEM-120 – PROG – EN

13

 Factory 

setting

NORMAL 

OPERATION

REVERSED 

OPERATION

NORMAL 

OPERATION

NORMAL 

OPERATION

REVERSED 

OPERATION

 

CHOICE OF RADIATOR FLUID LEVEL PROBE.

 

DESCRIPTION

CHOICE OF PROBES

CHOICE 

OF PROBES

CHARGING ALTERN.

ANOMALY

NUMBER OF STARTUP

ATTEMPTS

OIL PRESSURE LOW

WARNING

START WITH

FLAT BATTERY

RADIATOR 

LEVEL PROBE

NO

FUEL

95°C

NO STOP

NO STOP

100°C

PROGRAM ONE LEVEL AT A TIME

ENGINE OVERTEMPERATURE WARNING.

 

CHARGING ALTERNATOR FAULT.  It is possible to program the stop; by factory default it is programmed to stop.

NUMBER OF ATTEMPTS TO START.  10 attempts to start can be programmed. (Failure to start).

LOW OIL PRESSURE WARNING. (The pressure measured by the pressure transmitter). This is programmed as notification and does 

not stop the engine. (The low pressure detected by the pressure switch causes the engine to stop).

STARTING OF GENERATOR SET WITH BATTERY WITH LOW CHARGE.  (With control unit in automatic mode). Starts or stops the 

generator set depending on the voltage measured at the battery terminals.

FUEL RESERVE.  

Does not stop the engine.

FUEL FINISHED

.  It is possible to program the stop; by factory default it is programmed to stop.

OVERTEMPERATURE. 

 

Press when the arrow is 

next to the parameter to be modified

 

Press when the arrow is 

next to the parameter to be modified

 

Press when the arrow is 

next to the parameter to be modified.

 

Press when the arrow is 

next to the parameter to be modified

 

Press when the arrow is 

next to the parameter to be modified

 

Press to choose.

 

Press when the arrow is 

next to the parameter to be modified

 

Press when the arrow is 

next to the parameter to be modified

Press and wait for 

the system to write 

PROGRAMMED.

THIS IS

DISPLAYED

ON THE DISPLAY

THIS IS

DISPLAYED

ON THE DISPLAY

Press to 

display.

Stop

of engine

Delay

in intervention

Delay

in intervention

Delay

in intervention

Stop

of engine

Stop

of engine

Decreases

Number

of attempts

Increases

INTERVENTION DUE TO ENGINE OVERTEMPERATURE. The temperature is measured by the (TEMPERATURE) TRANSMITTER and is 

programmable. The protection device can be set on two levels and intervenes when these are exceeded. The warning level is 

programmed only as notification, the other level is programmed to stop the engine (the overtemperature is also detected by the 

thermostat that always causes the engine to stop).

Threshold

Threshold

Minimum threshold

Maximum threshold

Threshold

Threshold

        

 

 STOP

RADIATOR

CORE

IN THE ABSENCE OF

LIQUID, 

REMOVES

THE 

GROUND SIGNAL

THE CONTROL UNIT IS 

PROGRAMMED FOR 

NORMAL OPERATION

RADIATOR

CORE

IN THE ABSENCE 

OF LIQUID, 

ACTIVATES

THE 

GROUND SIGNAL

• FUEL

  RESERVE (10%)

• FUEL

  FINISHED (1%)

95°C/203°F 

NO STOP

100°C/212°F 

                   

1% 

 3  s.STOP

0.5Bar/500Kpa 

 1 s 

12.4Volt  

   13.6

 1200 s 

12.4Volt  13.6

 1200 s 

0.5Bar

 1 s 

1% 

 3 s  STOP

Press to 

display.

Press to 

display.

Press to 

display.

Press to 

display.

Press to 

display.

Press to 

display.

Press and wait for 

the system to write 

PROGRAMMED.

Press and wait for 

the system to write 

PROGRAMMED.

Press and wait for 

the system to write 

PROGRAMMED.

Press and wait for 

the system to write 

PROGRAMMED.

Press and wait for 

the system to write 

PROGRAMMED.

Press and wait for 

the system to write 

PROGRAMMED.

Press and wait for 

the system to write 

PROGRAMMED.

Press to 

display.

OVERHEATING

WARNING

OVERHEATING

ENGINE

4

4

Summary of Contents for CEM-120

Page 1: ...SRL Parma CEM 120 PROG EN 1 COMBINED CONTROL UNIT FOR CONTROLLING AN INDEPENDENT GENERATOR SET AND IRRIGATION MOTOR PUMP TYPE CEM 120 RESERVED FOR THE MANUFACTURER TECHNICAL PROGRAMMING OPERATIONS MA...

Page 2: ...UNIT STAND BY After 30 seconds of inactivity the control unit enters STAND BY and completely switches off all the notifications led and display To exit STAND BY press one of the buttons RESTORATION OF...

Page 3: ...rogrammed fuel float Programming of the ohmic values of the pressure transmitter Procedure for switching instruments on and off Procedure for deleting the switching off Programming of ohmic values of...

Page 4: ...AGE The preset language is Italian the selectable languages are ENGLISH FRENCH GERMAN SPAIN PORTUGUESE SELECT LANGUAGE ENGLISH ENGLISH Press to select the language Press and wait for the system to wri...

Page 5: ...s the test cycle GENERATOR FREQUENCY Press to choose Press to choose Press to choose Press to choose Press to choose Factory setting Factory setting Factory setting Factory setting Factory setting REA...

Page 6: ...o stop and message describing the fault or 2 Disabling of control unit protection devices when the input is connected to ground only the following protection devices remain active OVERSPEED OVERFREQUE...

Page 7: ...n needs to be carried out but if it is necessary to carry it out stop the engine Run the engine at a costant and known rpm value for example by means of a portable revolution counter Run the engine at...

Page 8: ...er reaches the programmed value Notification number 4 is cyclic and triggers after the programmed hours and whole multiples of them The request for maintenance is indicated by the flashing of the hour...

Page 9: ...tinuous operation WEEKLY SELF TEST DURATION When the test time expires the engine stops 1 to 60 minutes 3 minutes INSUFFICIENT INTERVENTION TIME OR PUMP WATER OVERPRESSURE after the increase or loweri...

Page 10: ...h no time limits INSUFFICIENT INTERVENTION TIME OF PUMP WATER OR PUMP WATER OVERPRESSURE After the increase or lowering of pump water pressure and when this time has expired the stopping process begin...

Page 11: ...switch no programming is possible 133 FAILURE TO STOP AFTER STOP CON TROL 60 YES See description on page 5 of the user instruction manual no programming is possible 135 LOW LEVEL IN RADIATOR ALWAYS AC...

Page 12: ...he connections of the mains phases are incorrect The generator contactor is not closed no programming is possible 231 G S ASYMME TRY OUT OF RANGE 5 to 20 15 1 to 600 15 YES YES STOPS The percentage di...

Page 13: ...next to the parameter to be modified Press when the arrow is next to the parameter to be modified Press and wait for the system to write PROGRAMMED THIS IS DISPLAYED ON THE DISPLAY THIS IS DISPLAYED...

Page 14: ...AGE PRESENT G S UNDERFREQUENCY G S OVERFREQUENCY G S OVERVOLTAGE Press when the arrow is next to the parameter to be modified Press when the arrow is next to the parameter to be modified Press when th...

Page 15: ...urrent triggers the intervention at 100A but only when the current transformer withstands this current PUMP PROGRAMMING G S OVERLOAD WARNING DIFFERENTIAL OVERPRESSURE G S OVERLOAD G S DOES NOT SUPPLY...

Page 16: ...24 140 156 170 Press to display choice of pressure transmitters Press and wait for the system to write PROGRAMMED PROGRAMMABLE PRESSURE TRANSMITTER Press and wait for the system to write PROGRAMMED PR...

Page 17: ...E VALUES OHM TEMPERATURE TRANSMITTERS PRESSURE TRANSMITTERS Decreases Increases Decreases Increases By factory default the control unit is set for pressure and temperature transmitters TYPE TPO 403 Pr...

Page 18: ...rol unit is programmed for a float with rheostat suitable for FUEL LEVEL indication MANAGEMENT OF FUEL W It is possible to program the use of a float with contact that closes to ground when there is n...

Page 19: ...ction GENERAL ALARM switching off is possible when this intervenes to warn of an imminent automatic start up except for a call start up It cannot be switched off when the intervention is caused by a f...

Page 20: ...rds control units can be addressed SERIAL PORT RS232 MOD BUS GSM MODEM Select GSM 9600 bps to activate the connection with the telephone number to be notified when the G S is in alarm condition Press...