ELCOS CEM-120 Technical Programming Operations Manual Download Page 7

 ELCOS SRL 

- Parma - CEM-120 – PROG – EN

7

SIGNALS COMING FROM THE CHARGING ALTERNATOR

RUNNING ENGINE THRESHOLD, TACHOMETER, OVERSPEED AND UNDERSPEED ADJUSTMENTS

ADJUSTMENTS WITH CHARGING ALTERNATOR FREQUENCY (W)

TACHOMETER ADJUSTMENT

SIGNALS COMING 

FROM THE GENERATOR

SIGNALS COMING 

FROM THE PICK-UP MAGNETIC TRANSDUCER (control unit terminals 63 - 64) 

ADJUSTMENT OF RUNNING ENGINE THRESHOLD

Normally no adjustment needs to be carried out, but if it is necessary to carry it out: stop the engine.

Choose the voltage threshold coming from the charging alternator (terminal D+).

Adjustment range 3 to 12 (12V)  6 to 24 (24V). Factory setting 7V (14V).

Factory setting 7V, 14V.

OVERSPEED ADJUSTMENT

RUNNING ENGINE 

THRESHOLD 66

 

RUNNING ENGINE 

THRESHOLD RPM

 

OVERSPEED

7 V

600 RPM

7 V

600 RPM

1860 RPM

1860 RPM

Decreases 

  

 

Increases

Press to choose the voltage thresh-

old.

 

  

 

Press to choose at how many revs 

you want to disable the starter motor.

Adjustment range 300 to 4000 RPM.

 

 

Press to choose the

 overspeed threshold.

Adjustment range 1530 to 5100 RPM.

Press to 

display

.

 Factory setting

 Factory setting

 Factory setting

Threshold

          

          

NECESSARY PROGRAMMING

  (With terminal 65 of the control unit 

           connected)

ADJUSTMENT OF RUNNING ENGINE AND OVERSPEED 

with signals coming from the W of the charging alternator (control unit terminal 65)

PICK-UP 

(control unit terminals 63-64)

ADJUSTMENT OF RUNNING ENGINE THRESHOLD 

- first carry out tachometer adjustment

Normally no calibration needs to be carried out, but if it is necessary to carry it out: 

stop the engine.

Run the engine at a costant and known rpm value

(for example by means of a portable revolution counter).

Run the engine at a costant and known rpm value

(for example by means of a portable revolution counter).

• ADJUSTMENT OF RUNNING ENGINE THRESHOLD no adjustment

• TACHOMETER ADJUSTMENT see page 5 ADJUSTMENT OF TACHOMETER WITH GENERATOR FREQUENCY

• OVERFREQUENCY ADJUSTMENT - see page 12 GENERATOR OVERFREQUENCY

TACHOMETER ADJUSTMENT

          

          

NECESSARY PROGRAMMING

  (With terminals 63-64 of the control 

           unit connected)

PICKUP CALIBRAT.

3,000 RPM

Press and wait for the system to 

write PROGRAMMED. 
To stop press button 

 

PICKUP CALIBRAT. 

PRESS START

With this signal do not connect terminal 65

Setting 

with control unit 

connected to D+ 

(control unit

terminal 66)

of the 

pre-excitation 

alternator.

Setting with 

control unit

connected to 

the W 

(

control unit 

terminal 65

of the pre-exci-

tation alternator 

or to the 

yellow wire 

of the perma-

nent magnet 

alternator.

Press to 

display.

Press to 

display.

Press and 

wait for the 

system to write 

PROGRAMMED.

Press to 

display.

Press and 

wait for the 

system to write 

PROGRAMMED.

Press and 

wait for the 

system to write 

PROGRAMMED.

Start the engine

whit the button 

.

PICKUP CALIBRAT.

3000 RPM

PROGRAMMING

Set the rpm of the engine 

read on the portable 

tachometer.

  

 

 Factory setting

RPM/W CALIB. 

PRESS START

Press to 

display.

Start the engine

whit the button 

.

RPM/W CALIB.

3000 RPM

Set the rpm of the engine 

read on the portable tacho-

meter.

  

 

RPM/W CALIB.

3000 RPM

Press and wait for the system to 

write PROGRAMMED. 
To stop press button 

 

 Factory setting

Summary of Contents for CEM-120

Page 1: ...SRL Parma CEM 120 PROG EN 1 COMBINED CONTROL UNIT FOR CONTROLLING AN INDEPENDENT GENERATOR SET AND IRRIGATION MOTOR PUMP TYPE CEM 120 RESERVED FOR THE MANUFACTURER TECHNICAL PROGRAMMING OPERATIONS MA...

Page 2: ...UNIT STAND BY After 30 seconds of inactivity the control unit enters STAND BY and completely switches off all the notifications led and display To exit STAND BY press one of the buttons RESTORATION OF...

Page 3: ...rogrammed fuel float Programming of the ohmic values of the pressure transmitter Procedure for switching instruments on and off Procedure for deleting the switching off Programming of ohmic values of...

Page 4: ...AGE The preset language is Italian the selectable languages are ENGLISH FRENCH GERMAN SPAIN PORTUGUESE SELECT LANGUAGE ENGLISH ENGLISH Press to select the language Press and wait for the system to wri...

Page 5: ...s the test cycle GENERATOR FREQUENCY Press to choose Press to choose Press to choose Press to choose Press to choose Factory setting Factory setting Factory setting Factory setting Factory setting REA...

Page 6: ...o stop and message describing the fault or 2 Disabling of control unit protection devices when the input is connected to ground only the following protection devices remain active OVERSPEED OVERFREQUE...

Page 7: ...n needs to be carried out but if it is necessary to carry it out stop the engine Run the engine at a costant and known rpm value for example by means of a portable revolution counter Run the engine at...

Page 8: ...er reaches the programmed value Notification number 4 is cyclic and triggers after the programmed hours and whole multiples of them The request for maintenance is indicated by the flashing of the hour...

Page 9: ...tinuous operation WEEKLY SELF TEST DURATION When the test time expires the engine stops 1 to 60 minutes 3 minutes INSUFFICIENT INTERVENTION TIME OR PUMP WATER OVERPRESSURE after the increase or loweri...

Page 10: ...h no time limits INSUFFICIENT INTERVENTION TIME OF PUMP WATER OR PUMP WATER OVERPRESSURE After the increase or lowering of pump water pressure and when this time has expired the stopping process begin...

Page 11: ...switch no programming is possible 133 FAILURE TO STOP AFTER STOP CON TROL 60 YES See description on page 5 of the user instruction manual no programming is possible 135 LOW LEVEL IN RADIATOR ALWAYS AC...

Page 12: ...he connections of the mains phases are incorrect The generator contactor is not closed no programming is possible 231 G S ASYMME TRY OUT OF RANGE 5 to 20 15 1 to 600 15 YES YES STOPS The percentage di...

Page 13: ...next to the parameter to be modified Press when the arrow is next to the parameter to be modified Press and wait for the system to write PROGRAMMED THIS IS DISPLAYED ON THE DISPLAY THIS IS DISPLAYED...

Page 14: ...AGE PRESENT G S UNDERFREQUENCY G S OVERFREQUENCY G S OVERVOLTAGE Press when the arrow is next to the parameter to be modified Press when the arrow is next to the parameter to be modified Press when th...

Page 15: ...urrent triggers the intervention at 100A but only when the current transformer withstands this current PUMP PROGRAMMING G S OVERLOAD WARNING DIFFERENTIAL OVERPRESSURE G S OVERLOAD G S DOES NOT SUPPLY...

Page 16: ...24 140 156 170 Press to display choice of pressure transmitters Press and wait for the system to write PROGRAMMED PROGRAMMABLE PRESSURE TRANSMITTER Press and wait for the system to write PROGRAMMED PR...

Page 17: ...E VALUES OHM TEMPERATURE TRANSMITTERS PRESSURE TRANSMITTERS Decreases Increases Decreases Increases By factory default the control unit is set for pressure and temperature transmitters TYPE TPO 403 Pr...

Page 18: ...rol unit is programmed for a float with rheostat suitable for FUEL LEVEL indication MANAGEMENT OF FUEL W It is possible to program the use of a float with contact that closes to ground when there is n...

Page 19: ...ction GENERAL ALARM switching off is possible when this intervenes to warn of an imminent automatic start up except for a call start up It cannot be switched off when the intervention is caused by a f...

Page 20: ...rds control units can be addressed SERIAL PORT RS232 MOD BUS GSM MODEM Select GSM 9600 bps to activate the connection with the telephone number to be notified when the G S is in alarm condition Press...

Reviews: