ELCOS SRL
- Parma - CEM-120 – PROG – EN
19
SWITCHING OFF OF FUNCTIONS
(See procedure on previous page)
ON
OFF
•
MAN MODE (MANUAL)
AUT MODE (AUTOMATIC)
•
OFF MODE (LOCKED)
•
BATTERY UNDERVOLTAGE
•
BATTERY OVERVOLTAGE
•
OVERTEMPERATURE WARNING
•
ENGINE OVERTEMPERATURE (Measured by the temperature transmitter)
•
LOW OIL PRESSURE WARNING
•
FAILURE TO STOP
•
START WITH FLAT BATTERY
•
G.S. UNDERVOLTAGE
•
G.S. OVERVOLTAGE
•
G.S. UNDERFREQUENCY
•
G.S. OVERLOAD WARNING
•
G.S. OVERLOAD
•
G.S. DOES NOT SUPPLY POWER
•
INCORRECT G.S. PHASE SEQUENCE
•
G.S. ASYMMETRY OUT OF RANGE
•
STAND BY
•
PICK UP DISCONNECTED
•
SENDING OF SMS AT EACH START AND STOP - an SMS message is sent for each automatic
start-up or stop
•
SMS ON CHANGING TO AUT MODE
•
SMS ON CHANGING TO OFF MODE
•
SMS ON RESETTING CYCLIC MAINTENANCE - see description in modem attachment (B)
•
SMS ON FAULT RESET
•
CHARGING ALTERNATOR - for this switching off, also release the deflector and carry out the
procedure described on page 5; see ADJUSTMENT OF TACHOMETER WITH GENERATOR
FREQUENCY (switching off to be avoided, incomplete engine running detection)
•
GENERAL ALARM -
switching off is possible
when this intervenes to warn of an imminent
automatic start-up except for a call start-up.
It cannot be switched off
when the intervention is caused
by a fault.
•
12 24
VOLT
CHOICE OF CURRENT TRANSFORMER
It is possible to select current transformers from 30/5 up to 2000/5.
EXAMPLE
Press
to choose the value of the current
transformer.
AMP. TRANSFORMER
50/5
AMP. TRANSFORMER
100/5
G.S. OVERLOAD
WARNING
G.S.
OVERLOAD
95A
100A
PROGRAMMED
AUTOMATIC CALIBRATION (A. C.)
• GENERATOR OVERLOAD WARNING
• GENERATOR OVERLOAD
After the A. C. is programmed, the thresholds are automatically
adjusted.
The WARNING threshold is set at 95%,
the overload threshold is set at 100% of the nominal value of the
A. C.
To change the thresholds manually, refer to page 15
Press and wait for
the system to write
FAULT LOG
To reset press
simultaneously and
wait for the system
to write PROGRAMMED.
ANOMALIES
OCCURRED
N 12 h1501 20-05-
2014 17:30
LOW OIL
PRESSURE
RESET
LOG?
Press to
display.
Number
(progressive)
of faults
that have occurred
Date
Hour
meter
of engine
Time
Decreases
Increases
(Example)
COMPLETE RESET OF THE LOG
RESET
LOG?
The data of the last 100 faults that have stopped the engine are collected.
Press to
display.