 ELCOS – Parma – Italy – CAM-335 

Valid for firmware revision 1.14 and above   

Page 3 of 20

 

 

INSTRUCTIONS IN BRIEF 

 
 

 

 

 
 
 
 
 

INSTRUMENTS 

The  control  unit  has  a  backlit  128  x  64  dot  graphic  display  with  touch  screen.  It  is  used  to  view  the  following 
instruments: 

 

Three line-to-line mains/generator voltages. 

 

Three star mains/generator voltages. 

 

Three mains/generator ammeters. 

 

Mains/generator frequency meter. 

 

Active  (kW),  reactive  (kVAR)  and  apparent  (kVA)  power,  for  both  mains  and  generator.  The  powers  are 

displayed for each phase and as a sum of the phases. 

 

Mains/generator power factor indicator displayed for each phase. 

 

Mains/generator energy counter (kWh). 

 

Battery voltage. 

 

D+ voltage (pre-excitation alternator). 

 

Fuel tank level indicator. 

 

Engine temperature expressed in °C or °F. 

 

Oil pressure expressed in BAR or kPa. 

 

Engine revolutions (RPM). 

 

Total hour-meter. 

 

Partial hour-meter. 

 

Start-ups count. 

 

Starting failure counter. 

 

Maintenance expirations. 

 

Rental hours expirations. 

 

Calendar clock. 

 

Automatic test. 

All the instruments for the mains (V, A, Hz and kW) are also displayed simultaneously. Simply pressing the arrows 

displays all electrical instruments for the generator and engine. In the event of an anomaly, the display presents the 
message indicating the anomaly that has occurred. 

Display with 
touch screen 

Press to start 
in manual 
mode 

Press to stop 
in manual 
mode 

Cumulative 
alarm without 
stop (yellow) 
with stop 
(red) 

Power from 
mains 
present 

Mains 
inserted on 
power user 

Generator 
inserted on 
power user 

Power from 
generator 
present 

Control unit is 
on: 

 

manual 

 

automatic 

 

test 

 

off 

Press to select 
function: 

 

manual 

 

automatic 

 

test 

 

off (failure reset) 

 

programming 

Engine running 

Buttons to switch the 
power user to mains 
or generator (in 
manual mode). 

Press the arrows to browse display menus. 
Acknowledging the general alarm

Summary of Contents for CAM-335

Page 1: ...messages Complete three phase voltmetric control of mains and genset undervoltage overvoltage phase asymmetry incorrect phase sequence underfrequency and overfrequency Texts in 7 languages Italian Eng...

Page 2: ...e manual as an attachment CHRONOLOGY OF MANUAL REVISIONS Date Revision Description Page 27 07 2015 1 00 First release 05 09 2016 1 05 MAX mains voltage present delay 9999 sec 12 technical prog 10 10 2...

Page 3: ...d in C or F Oil pressure expressed in BAR or kPa Engine revolutions RPM Total hour meter Partial hour meter Start ups count Starting failure counter Maintenance expirations Rental hours expirations Ca...

Page 4: ...t if function is enabled Anomalies Clock Information about the control unit The two arrows are used to scroll through the instrument groups on the display or to select the sub menus under the settings...

Page 5: ...nts individually simply touch the display on the relevant instrument For example touching the D icon with your finger opens the menu that displays the individual instrument To move inside the groups o...

Page 6: ...engine running and with correct generator voltage and frequency once the G S VOLTAGE PRESENT DELAY has elapsed the generator contactor is closed When operating the genset is protected from any anomali...

Page 7: ...ot be run if there is an anomaly The automatic test can be performed in two ways WEEKLY the test will be run weekly at the time and on the day set MEASURED the test can be programmed to run at cycles...

Page 8: ...set beforehand If programmed stopping is also achieved with PROTECTION IN MANUAL bypassed and with the PROTECTION INHIBITION input active The procedure for resetting expired maintenance is to be perfo...

Page 9: ...rticular problem occurred in the engine If CAN Bus line connection between the two control units is interrupted the message CAN Bus ANOMALY will appear The instruments managed and displayed by the CAM...

Page 10: ...ge asymmetrical voltages incorrect phase sequence under frequency and overfrequency Mains voltmetric relay when each parameter has been accepted individually after the mains voltage present delay has...

Page 11: ...7 levels is given below 1 The operator can read all the settings but cannot edit them 2 Access in editing mode to rental hours and history log from maintenance hours 3 Access only for resetting expir...

Page 12: ...________________________________________________________________ ELCOS Parma Italy CAM 335 Valid for firmware revision 1 14 and above Page 12 of 20 CONNECTION DIAGRAM Basic diagram for illustration pu...

Page 13: ...re cable not longer than 40 metres For additional details request the diagrams for the specific engines In the manual for the control unit ECU ECM read if inserting the 120ohm 1 4W termination resisto...

Page 14: ...he programming items For example Press to confirm the selection The following appears Wait for a few seconds The chosen parameter is now programmed in the control unit The settings are stored in a non...

Page 15: ...r When programming a binary parameter enabled disabled for example enabling the weekly automatic test press to enable or disable the parameter For example or Press to confirm the value Programming a n...

Page 16: ...W 100 PR ENGLISH FRENCH GERMAN SPANISH PORTUGUESE CUSTOM CLOCK CALENDAR Standard Calendar clock adjustment TELEPHONE NUMBERS TELEPHONE 1 16 digits Empty Telephone numbers to which text messages will b...

Page 17: ...NERATOR NOT DELIVERING Although running the genset does not deliver voltage 228 GENERATOR CONTACTOR FAULT The generator contactor does not open or close 230 GENERATOR PHASE SEQUENCE The sequence of th...

Page 18: ...asurement range 45 85Hz Accuracy 0 1Hz Amperometric inputs Measurement range 20mA 6Aac Amperometric transformer ratio 5 Maximum displayable current 4800Aac Accuracy 1 Digital outputs Type of output Po...

Page 19: ...nical strain Do not let cuttings of copper conductors or other metal residues drop onto the control unit Never disconnect the battery terminals while the engine is running Strictly avoid using a batte...

Page 20: ...UEST Type Item Code EXPANSION MODULE MDE 088 00242269 ETHERNET INTERFACE ZE 100 00070227 GSM MODEM AMD RB900 PRO 00070218 Programming software ZW SMART 00070212 DOCUMENTATION ON REQUEST Downloadable f...

Reviews: