Select the MANUAL operating mode, start the motor pump with button
.
Set the required pressure with buttons
after 10 seconds
BAR STORED
is displayed.
Wait until the pipes are filled and the pressure has stabilized at the chosen value. After finishing setting, SELECT OPERATING
MODE
, the pressure of the system will remain set at the chosen pressure.
The chosen pressure value can be corrected with the system under pressure, by pressing buttons
.
The working pressure setting is deleted, when the engine is stopped by selecting operating mode
.
SEQUENCE OF OPERATIONS
start up
running pump
PRIMING
IN PROGRESS
OVERPRESSURE remains set to two bars, this value is
added to the working pressure
(for example, working pressure 9 bars overpressure 11 bars)
Wait until the pipes are filled.
When the working pressure has
stabilized, select
.
The working pressure
is regulated automati
-
cally.
Set the required
pressure.
Press to select the
pump water pressure
gauge.
example
Working
pressure
PUMP PROTECTION
N
O ADJUSTING IS REQUIRED.
Pump water
overpressure
or
Insufficient
pressure
(subpressure)
INSUFFICIENT
PRESSURE
OVERPRESSURE
However it is possible to change the
two bars
of pressure
lowering (subpressure), by pressing button
.
This change is deleted, when the engine is stopped, by selecting the
OFF/RESET operating mode.
WORKING PRESSURE
Press to
set the sub-
pressure value
(PRESSURE
SWITCH)
Press to select the
pump water pressure
gauge
FAILURE TO FILL PIPES FAULT
The acceleration starts with the engine running, with pump primed.
The motor pump reaches the redefined WORKING PRESSURE (see
BARS STORED
) within the TIME OF FAILURE TO
FILL PIPES, set to 120 seconds. If air is present in the pipes, the acceleration will be alternated with pauses (of 15 seconds), if
the pressure remains steady for 5 seconds. This situation will be repeated several times until the WORKING PRESSURE is rea
-
ched. If the pressure is not reached within the FAILURE TO FILL PIPES time (120 sec.), FAILURE TO FILL PIPES is displayed
on the display and the engine stops.
ABNORMAL ACCELERATION
(Pipe leakage controlled within the limits of the system).
As a result of a leakage, the engine tends to increase the revolutions to bring it back to WORKING PRESSURE. If the revolutions
increase by 10% for a time longer than 120 seconds, ABNORMAL ACCELERATION is displayed on the display and the engine
stops
WORKING PRESSURE CONTROL
9
9
PRESSOSTAT
BAR 6
Always on: pump primed.
Flashing: failure to prime.
The pump protection is enabled when warning lights PUMP PROTECTION ACTIVE and water pressure normal come on
after the water pressure has remained stable for 2 consecutive minutes, in any case 10 minutes after the engine started.
Intervention of the protection (5 seconds after the pressure goes up or down by
two bars
) stops the engine and is
shown on the display:
Factory Setting
The motor pump starts up if
the motor pump is primed.
The priming probe senses
water presence (pump primed).
Select
MAN
Automatic
pump
priming.