ELCOS 00211143 Instruction And User'S Manual Download Page 4

 ELCOS SRL 

- Parma - CIM-137/4G - 137/4GW - MAN - EN

4

Select the MANUAL operating mode, start the motor pump with button  

  . 

Set the required pressure with buttons     

after 10 seconds  

BAR STORED

  is displayed.

Wait until the pipes are filled and the pressure has stabilized at the chosen value. After finishing setting, SELECT OPERATING 

MODE  

, the pressure of the system will remain set at the chosen pressure. 

The chosen pressure value can be corrected with the system under pressure, by pressing buttons              

 

 .

The working pressure setting is deleted, when the engine is stopped by selecting operating mode 

.

SEQUENCE OF OPERATIONS

start up

running pump

PRIMING

IN PROGRESS

OVERPRESSURE remains set to two bars, this value is 

added to the working pressure

(for example, working pressure 9 bars overpressure 11 bars)

  

Wait until the pipes are filled.

When the working pressure has 
stabilized, select   

  .

The working pressure

is regulated automati

-

cally.

Set the required 

pressure.

Press to select the

pump water pressure 

gauge.

example

Working

pressure

PUMP PROTECTION

       N

O ADJUSTING IS REQUIRED.

Pump water

overpressure

or

Insufficient 

pressure

(subpressure)

INSUFFICIENT

PRESSURE

OVERPRESSURE

However it is possible to change the 

two bars

  of pressure

lowering (subpressure), by pressing button         

 .

This change is deleted, when the engine is stopped, by selecting the 

OFF/RESET operating mode.

WORKING PRESSURE

Press to

set the sub-

pressure value

(PRESSURE

SWITCH)

Press to select the

pump water pressure 

gauge

FAILURE TO FILL PIPES FAULT

The acceleration starts with the engine running, with pump primed.

The motor pump reaches the redefined WORKING PRESSURE (see  

BARS STORED

  ) within the TIME OF FAILURE TO 

FILL PIPES, set to 120 seconds. If air is present in the pipes, the acceleration will be alternated with pauses (of 15 seconds), if 

the pressure remains steady for 5 seconds. This situation will be repeated several times until the WORKING PRESSURE is rea

-

ched. If the pressure is not reached within the FAILURE TO FILL PIPES time (120 sec.), FAILURE TO FILL PIPES is displayed 

on the display and the engine stops.

ABNORMAL ACCELERATION

(Pipe leakage controlled within the limits of the  system).

As a result of a leakage, the engine tends to increase the revolutions to bring it back to WORKING PRESSURE. If the revolutions 

increase by 10% for a time longer than 120 seconds, ABNORMAL ACCELERATION is displayed on the display and the engine 

stops

WORKING PRESSURE CONTROL

          

9

           

9

PRESSOSTAT

BAR 6

 

Always on: pump primed.

      Flashing: failure to prime.

The pump protection is enabled when warning lights PUMP PROTECTION ACTIVE   and water pressure normal     come on 

after the water pressure has remained stable for 2 consecutive minutes, in any case 10 minutes after the engine started.

Intervention of the protection (5  seconds  after  the  pressure  goes  up  or  down  by        

 two bars

  ) stops the engine and is 

shown on the display:  

 

Factory Setting

The motor  pump starts up if 

the motor pump is primed.

The  priming probe senses 

water presence (pump primed).

Select 

MAN

Automatic 

pump

priming.

Summary of Contents for 00211143

Page 1: ...pressure of the system constant accelerator with 2 wires connected to the control unit Controls the flow of water in the pipe Electronic pressure switch to control the pump water pressure Digital pum...

Page 2: ...SPLAY CHANGES HOLD DOWN TO SI LENCE THE GENERAL ALARM BUZZER PRESS UNTIL THE 2 SIGNS START FLASHING TO EXCLUDE PUMP PROTECTION TO RE ACTIVATE PROTECTION PRESS AGAIN UNTIL THEY SWITCH OFF PRESSTOSTART...

Page 3: ...iming Pump priming failure 5 Operation Clutch Engine warming Engine cooling Stop Emergency stop Stop with the Stop and Off Reset buttons Stopping failure Buzzer 6 Operation Timer Resetting of the set...

Page 4: ...SSURE SWITCH Press to select the pump water pressure gauge FAILURE TO FILL PIPES FAULT The acceleration starts with the engine running with pump primed The motor pump reaches the redefined WORKING PRE...

Page 5: ...if the pump has not started up after the fourth pulse It is obtained with measurement of the voltage and frequency of the battery charging alternator Disables the starter motor The priming pump start...

Page 6: ...ng buttons the engine stops after slow deceleration Stopping can be obtained in two ways With electromagnet de energized with engine running and energized with it stopped remaining in this condition f...

Page 7: ...display the end of work time indicator comes on The work time is set by pressing the push button lights up until the desired value appears on the DISPLAY On releasing the push button the timer automat...

Page 8: ...th running engine 2 YES SLOW YES WITH STOP The temperature detected by the transmitter exceeds the set threshold FUEL RESERVE FUEL RESERVE Flashing FUEL FLOAT TERMINAL T Always active 5 10 NOT NOT DOE...

Page 9: ...of the intervention delay INSUFFICIENT PUMP WATER PRESSURE INSUFFICIENT WATER PRES SURE ELECTRONIC PRESSURE SWITCH After detection of working pressure and in any case 600 after the pump started 5 YES...

Page 10: ...OWN only for permanent magnet WHITE YELLOW ORANGE BLACK BATTERY STOP SYSTEMS SEE PAGE 11 ORANGE BLUE INDICA TOR W RESERVE ACCELERATOR YELLOW GREEN BLACK BLUE ORANGE BROWN WHITE VIOLET CABLE 1 5m BLACK...

Page 11: ...ER and the oil PRESSURE GAUGE connect the transmitters to the respective wires of the unit then CUT and isolate the BLACK VIOLET wire WARNING IT IS NOT POSSIBLE TO MOUNT THE EMERGENCY STOP BUTTON ON A...

Page 12: ...g pump P2 starts when the water reaches the priming probe lthe pump stops PRIMING FAILURE The pump is stopped if the priming probe does not sense the presence of water within 240 sec To connect PUMP P...

Page 13: ...hased from a telephone provider on any contract the PIN needs to be disabled To do this it is necessary to insert the SIM in a normal private use cell phone then enter the PIN supplied by the provider...

Page 14: ...ght left Push to view the first second or third subscriber Press and wait for OK to be written MOB 1 MOB 1 123456789 333456789 NOTIFIED MOB 1 333 Notifies via SMS message when the motor pump is in ala...

Page 15: ...ion exclusion After the switch off command the following is displayed After the command to delete switching off the following is displayed After the command the following is displayed After the comman...

Page 16: ...stopped STOP MOTOR PUMP START WATER PRESSURE HOURS OF OPERATION FUEL FAULT The fuel fault depends on any change in the fuel level in the motor pump tank when the engine is stopped The check up is ena...

Page 17: ...CONTROL UNIT IS NOT SUITABLE FOR OPERATING IN THE FOLLOWING CONDITIONS Where the environmental temperature is outside the limits indicated in the Technical Data Where the air pressure and temperature...

Page 18: ...tes Decreases Increases Decreases Increases Set the engine revolutions read on the portable tachometer Press and wait for OK to be written Press and wait for OK to be written Press and wait for OK to...

Page 19: ...ming pump yellow blue pump clutch white yellow 3A 40A 3A 3A 3A 3A Temperature range 10 60 C MODEM B1 B3 B5 B7 B8 B20 FDD LTE B1 B5 B8 WCDMA B3 B8 GSM Hour meter 4 digits Engine oil pressure gauge 0 9...

Page 20: ...Flow switch FAP 200 00500312 ORDERING DATA ACCESSORIES SUPPPLIED Type CIM 137 4G CODE 00211143 CIM 137 4GW CODE 00211151 PRE WIRED CONNECTOR CIM 130 1 6 7 CODE 70804397 TRANSMITTER TYPE TPA 200 CODE 7...

Reviews: