elco Thision EVO WH 250-120 Operation And Installation Manual Download Page 19

Commissioning 

Prepare water heater for first startup 

19 

 B  

  C 

 E      F 

Legend: 

A  On/off switch 

B  Return (ESC) 

C  Room temperature control 

D  Confirmation (OK) 

E  Manual mode 

F  Chimney sweeper mode 

G  Info mode 

H  Reset button 

I  Operation mode heating zone(s) 

L  Display 

M  Operation mode DHW 

Preparation for first startup 

Open the gas supply; 
Enable the power supply to the boiler; 
Switch on the boiler with the on/off 

switch (1); 
Make sure the boiler is in standby 

mode (

K

); 

Check the pump operation: make 

sure the pump runs in the right 

direction; 
Release all air from the pump motor. 

It‘s recommended to put the boiler on 

50% load after the first startup, as this 

is the best starting point to do a proper 

combustion analysis. This can be done 

with the following procedure: 

Push button I >3 Sek, the boiler goes 

into controller Stopp mode. 
Push the Info button (G), the actual 

boiler load (%) appears in the display; 
Choose „set up“ (confirm with OK 

button), now the boiler load can be 

changed by rotating the wheel (C) 

and confirming the 50% setting with 

the OK button. 

After checking the combustion values 

(see next page), the controller Stopp 

mode can be stopped by pushing the 

control mode button (I) >3 Sek. 

Cylinder Diagnosis

It is possible to view the operational data of each of 

the Thision WH i.e. temperatures, this is achieved by 

holding the button on the cylinder controller for  

approximately 5 seconds. The diagnosis number is 

shown for 1 second then the value for 3 seconds.

The diagnosis setting can be exited by holding the button for 

5 seconds or if the button is not depressed for 10 minutes.

So software version
D0 Operating Status
D1    Current T1 temperature
D2 Current T2 temperature
D3    Current T3 temperature
D4 Current T4 temperature
D5 N/A
D6 Load pump P1 speed (rpm)
D7 Required temperature

Temperature Setting

The Thision WH is factory set for 60 C DHW flow and can 

be adjusted by 5 C by switching the unit off and back on 

whilst holding the control button on the PCB. 

º

º

Summary of Contents for Thision EVO WH 250-120

Page 1: ...Operation and Installation manual THISION EVO WH 08 2016 PAG THEWH01...

Page 2: ......

Page 3: ...0 21 Gas tightness check 21 Water heater shut down 21 Maintenance Checklist 25 Replacing the electrodes 25 Cleaning the condensate receptacle 26 Cleaning and refilling the syphon 26 Inspection of the...

Page 4: ......

Page 5: ...directive 2004 108 EEC EMC directive EN 483 Gas fired central heating boilers Type C boilers of nominal heat input not exceeding 70 kW EN 15420 Gas fired central heating boilers Type C boilers of nom...

Page 6: ...utory obligations This boiler has been tested and certified to comply with all necessary European directives and is CE marked and complies with 92 42 EEC Efficiency of Hot Water Boilers Directive 90 3...

Page 7: ...rol ling the speed of the fan As a re sult the venturi mixing system will adapt the gas ra o to the chosen fan speed in order to maintain the best possible combus on figures and therewith the best e c...

Page 8: ...installed from the system to the unit 1 230Vac electrical supply 2 Mains cold water supply 3 DHWS secondary flow pipework 4 DHWS secondary return pipework 5 Gas supply pipework 6 Condense drain pipewo...

Page 9: ...NOx level mg kWh 39 39 CO level max min mg kWh 99 11 88 5 Max permissible flue resistance Pa 244 134 Water volume l 6 0 9 0 Water pressure max min boiler module bar 8 1 8 1 Max water temperature High...

Page 10: ...us output at 60 C 250L storage Continuous operation at 60 C 1st hour continous output at 60 C 500L storage 10 min peak output at 60 C 500L storage L 687 818 L 1622 2413 L 1122 1913 10 Electrical Data...

Page 11: ...352 1 1 4 1 1 4 1 1 4 1 1 4 3 4 3 4 3 4 3 4 1 1 2 1 1 2 1 1 2 1 1 2 W 100 B1 D H1 H1 mm 1952 1821 1952 1821 11 J K L M N mm mm mm mm mm J K L M N 1100 1000 800 700 600 1100 1000 800 700 600 DHW Flow...

Page 12: ...ons 1 2 3 4 Condensate connection 5 After filling with water the syphon included in delivery should be installed to the connection 5 at the bottom of the water heater Connect the hose to the draining...

Page 13: ...nal regulations Construct the flue gas system as short as possible for maximum length see planner documentation Construct horizonal ways with a mini mum angle of 3 Air intake connection 8 The air inta...

Page 14: ...taining visibility iii Discharges at high level e g into a metal hopper and metal downpipe with the end of the discharge pipe is clearly visible tundish visible or not or onto a roof capable of withst...

Page 15: ...Sizing of copper discharge pipe D2 for common T P relief valve sizes Schematic discharge pipe arrangement Unvented Applications Worked example of discharge pipe sizing The example below is for a G1 2...

Page 16: ...16 Cylinder Controls Electrical Connections...

Page 17: ...been eliminated close the outlet Step 4 Check pipework for leaks Further Commissioning Once the system has been completely filled and vented the unit can be connected to the electrical supply All DHWS...

Page 18: ...nal posi on Make sure the syphon is filled before star ng the boiler in order to pre vent flue gases discharging through the condensate connec on Flue and air intake connec ons Check whether the flue...

Page 19: ...s in the display Choose set up confirm with OK button now the boiler load can be changed by rotating the wheel C and confirming the 50 setting with the OK button After checking the combustion values s...

Page 20: ...to full load and minimum load values Make sure that the boiler is set to automa c opera on and controller stop mode is disabled a er the combus on test is finished Combus on se ngs Adjustments must be...

Page 21: ...lt in a lockout no 28 The lockout should disappear as soon as the plug is placed back in posi on the boiler will restart Ionisa on electrode 4 Remove electrical connec on from the ionisa on electrode...

Page 22: ...1 sensor error 65 Room temperature 2 sensor error 70 Buffer storage tank temperature 1 sensor error 71 Buffer storage tank temperature 2 sensor error 72 Buffer storage tank temperature 3 sensor error...

Page 23: ...g temperature sensor error 324 BX same sensors 325 BX extension module same sensors 326 BX mixing group same sensors 327 Extension module same function 328 Mixing group same finction 329 Extension mod...

Page 24: ...less header address error 353 Common flow sensor B10 not available 371 Flow temperature 3 heating circuit 3 supervision 372 Limit thermostat heating circuit 3 373 Extension module 3 error collective e...

Page 25: ...quality of the system water as well as supply water Check the water flow rate through the boiler Check correct the combus on values at full and mimimum load with a combus on analyzer Check the gas pre...

Page 26: ...fresh water Mount the syphon back in the original posi on Inspec on of combus on chamber For inspec on of the combus on chamber the mixing system and burner must be disassembled Switch o the boiler a...

Page 27: ...yzer for example Test points Bolt connections Gaskets of mixing system etc Safety devices Check the functionality and the settings of all safety devices connected Consult the chapter commissioning Che...

Page 28: ...s p m u P Safety devices a W C g n i t t e s t i m i l h g i H ter flow sensor checked d e k c e h c r o s n e s s a g e u l F C g n i t t e s r e t i m i l p m e T Min gas pressure switch setting mba...

Page 29: ...f T lics Low velocity header Water pboiler kPa Plated heat exchanger Water flow m3 h Bypass boiler Pump setting Other Safety devices High limit setting C Water flow sensor checked Temp limiter settin...

Page 30: ...Service ELCO UK 3 Juniper West Fenton Way Southfields Business Park Basildon Essex SS15 6SJ Tel 01268 546700...

Reviews: