Automatic Furnace Controller LFL 1... / LGK 16...
The LGK 16… type controller is desi-
gned to control and monitor burners
working according to a stepwise or
modulating principle. A detailed functio-
nal description with technical data and
project planning information with
respect to the automatic combustion
controllers can be found in the annex
and in the documents
LFL 1...-7451 D
LGK 16...-7785 D
Functional diagram
LFL 1... / LGK 16...
A =
Starting type interval
A-B= Flame development interval
B =
Burner has reached operating
position
B-C= Burner operation
(heat generation)
C-D= regular shut-off
t1
Pre-ventilating time
t2
Safety time
t3
Pre-ignition time
t4
Fuel valve enable
t5
Load regulator enable
t11
„OPEN“ run time of air damper
t12
„CLOSE“ run time of air damper
R =
Temperature or pressure
controller
G =
Fan motor
Z =
Ignition transformer
BV=
Fuel valve(s)
LR=
Load regulator
LK=
Air damper
RV=
Steadily adjustable fuel valve
FS=
Signal of flame
ZBV= Ignition burner valve