EL.CO. S.R.L.  – ELK22MP

 

INSTRUCTIONS FOR USE 

- Ver.05 - 03/22 - PAG. 8 

The  regulator  then  performs  a  series  of  connected  system 
operations  to  calculate  the  most  suitable  PID  adjustment 
parameters. 
The duration of the Autotuning cycle is limited to a maximum of 12 
hours. 
If the process is not completed within 12 hours, the parameters will 
not  be  changed  and  display  show 

“Fail  Auto”

.  Holding  down  the 

key 

 return to normal operation. 

Is possible stop the autotuning process by hold down the key 

 for 

five seconds. 
The  values  calculated  by  the  AutoTuning  will  be  automatically 
stored by the device at the end of the proper run of the Autotuning 
cycle in the PID adjustment parameters.  
 
 
 

5.6 - ALARM FUNCTION 

In  the  control  mode,  you  can  activate  relative  minimum  or 
maximum,  absolute  minimum  or  maximum,  relative  window  with 
activation inside or outside window alarms. 
You can enter a hysteresis and a delay on the return of the alarm. 
Such  functions  may  be  useful  in  order  to  avoid  frequent 
interventions  of  the  outputs  especially  when  they  command 
compressors. 
The delay function is deactivated by programming 

“ALxD” 

on 0. 

The parameter 

“ALx”

 sets the alarm setpoint.. 

Set 

“O1F”

 = AL to associate output 1 with the alarm 1. 

Set 

“O2F”

 = AL to associate output 2 with the alarm 2. 

 

 

Example of operation with 

“AL1T”

 = Loab (minimum alarm) 

 

 

Example of operation with 

“AL1T”

 = HidE (relative maximum)

 

 

Example of operation with 

“AL1T”

 = LHdi (relative band in)

 

 

5.7 – SETTING MODULE ADDRES 

ELK22MP have 16 as default addres. At the startup of the system, 
ELK22DKP  will  be  in  communication  with  the  lowest addres  of  the 
full system. During normal operation will be accepted value from 1 
to  16.  Connect  one  ELK22MP  at  time  and set  the  ADR  parameter 
before connect the next ELK22MP.  
Example:  connect  and  power  up  the  first  ELK22MP,  program  the 
ADR parameter to 0, and power off the system. Connect the second 
ELK22MP  and  power  up  the  system  (or  only  the  ELK22MP),  and 

set  the  ADR  parameter  at  the  next  or  prefer  value,  but  it  will  be 
different of the last ADR set. 
 
 

6 - PROGRAMMABLE PARAMETERS TABLE

 

 
Below are all the parameters that the device can be equipped with. 
 

The hex address is only for ELK22MPE and ELK22MPM 
 
The address in decimal is also avaiable for better reading. 
 
Address  512  in decimal  (0x200  in hex) is  reserved  for  reading 
the product temperature. 

 

Descrizione

 

Range

 

Def.

 

Indirizzo 

hex

 

SP1

 

SetPoint  1  

SSP ÷ FSP 

0x00-0 

SENS

 

In-probe type: 
TCJ = Thermocouple 

TCK = Thermocouple 

TCS = Thermocouple 

ntc= Thermistor NTC 
103-AT2 
Ptc= Thermistor PTC 
KTY81-121 
P100= Thermal 
resistor Pt100 
0-10= 0-10V 
4-20= 4-20mA 

1 = TCJ   

2 = TCK 
3 = TCS 
4 = NTC 
5 = PTC 

6 = P100 

TCJ 

0x01-1 

DP

 

Number of decimals 

P100, 0-10,  

4-20: 

0 / 1 

 

0x02-2 

SSC

 

Minimum display 

-999 ÷ 1000 

-50 

0x03-3 

FSC

 

Maximum display 

-999 ÷ 1000  1000 

0x04-4 

UNIT

 

Temperature 
measurement unit 

0 = °C 

1 = °F 

°C 

0x05-5 

CA

 

Measure offset 

-100 ÷ 100 

0x06-6 

FIL.D

 

Display adjustment 
time 

 

0.5 

0x07-7 

CONT

 

Adjustment type: 
Pid= PID  
On.F= ON/OFF 
On.Fn= Neutral Zone 
(double action 
ON/OFF) 

0 = Pid 

1 = On.F 

2 = On.Fn 

On.F 

0x08-8 

AUTO

 

Enabling autotuning: 
OFF = Disabled 
1  =  Start-up  upon 
each switching on 

=  Start-up  upon 
the first switching 
on 

 = Manual Start-up 

OFF /  

1 ÷ 3 

OFF 

0x09-9 

BP 

 

Proportional band 
(PID adj.) 

1 ÷ 1000 

40 

0x0A-10 

TD

 

Integral time (PID 
adj.) 

0 ÷ 100.0 

sec. 

10.0  0x0B-11 

TI

 

Derivative time (PID 
adj.) 

0 ÷ 100.0 

sec. 

5.0 

0x0C-12 

TR1

 

Output time period 

0.5 ÷ 20.0 

sec. 

20.0  0x0D-13 

HPOS 

  Positive adjustment 

hysteresis 

0 ÷ 100 

0x0E-14 

HNEG

 

Negative adjustment 
hysteresis 

0 ÷ 100 

0x0F-15 

SSP

 

Setpoint setting lower 
limit 

SSC ÷ FSC 

-50 

0x10-16 

Summary of Contents for ELK22MP

Page 1: ...1 For normalized signals 4 20mA 0 10V It is designed for mounting on a din rail The ELK22MP series consists of 4 models 3 of these act as a centralizer and one of them as a slave The models of the ELK...

Page 2: ...he menu to select a module 5 4 red digits Process value during operation parameter selected during programming 6 4 green digits Setpoint value during operation value of the parameter selected during p...

Page 3: ...munication speeds adopted range from 1200 to 38400 baudrates and allow very satisfactory performances while remaining well below the limits imposed by the RS485 standard This allows the line to be wir...

Page 4: ...ters of the instrument can be read and written via serial communication The configurable parameters are found in Paragraph 6 4 WARNINGS FOR INSTALLATION AND USE 4 1 PERMITTED USE The device has been d...

Page 5: ...and a maximum of 1 to 31 slave devices A devices sequence that have ELK22MPM or ELK22MP as a centralizer must consist of a centralizer device and a maximum of 1 to 15 slave devices Two control units...

Page 6: ...must be the device to which the line is connected that must have the termination resistor To do this disconnect the resistance from the accessory and continue the line with the cables for RS485 as bel...

Page 7: ...programming the parameter Cont ON FN the parameter OxF H REG the parameter OyF C REG The adjustment operation operates on outputs depending on the measurement of the setpoint SP1 and hysteresis HPOS...

Page 8: ...nect one ELK22MP at time and set the ADR parameter before connect the next ELK22MP Example connect and power up the first ELK22MP program the ADR parameter to 0 and power off the system Connect the se...

Page 9: ...6 LHdo None 0x19 25 AL2 Alarm threshold SSP FSP 0 0x1A 26 HAL2 Hysteresis of alarm remedy 0 100 1 0x1B 27 AL2D Delay of alarm remedy 0 100 0 sec 0 0x1C 28 ADR Module address 1 16 16 0x1D 29 For each m...

Page 10: ...LSB byte 0 byte1 0x06 byte 2 byte 3 byte 4 byte 5 byte 6 byte 7 7 4 FUNCTION 7 READ ALLARM STATUS The request has the following frame Slave number Function number CRC LSB MSB byte 0 byte1 0x07 byte 6...

Page 11: ...the following frame Slave number Function number First word address MSB LSB Value to write MSB LSB byte 0 byte1 0x06 byte 2 byte 3 byte 4 byte 5 The normal reply is merely an echo of the request messa...

Page 12: ...ay outputs and front reinforced between low voltage parts 24 and 240 power supply and relay outputs and low voltage parts static inputs and outputs reinforced between power supply and relay outputs re...

Page 13: ...ption of the probe Check that the probe is correctly connected to the device and then verify that the probe is working properly 11 2 CLEANING It is recommended to clean the device only with a slightly...

Reviews: