background image

EL.CO. S.R.L.  – ELK22MP

 

INSTRUCTIONS FOR USE 

- Ver.05 - 03/22 - PAG. 2 

Via RS485 (only for ELK22MPM)

 

Via Ethernet (only for ELK22MPE)

 

Programming with RS485 or Ethernet can be done via, for example, 
operator panel, PLC or computer. 
We will indicate "external instrument" the set of all the instruments 
that can connect to the centralizing devices. 
The programming phases must reflect these steps: 

Only one centralizing device

 

o

 

Power on the device

 

o

 

Programming  the  centralizing  device  with  the 
external device

 

o

 

Use the device

 

One centralizing devica with N slave device

 

o

 

Power on the centralizing deivce

 

o

 

Programming  the  centralizing  device  with  the 
external device

 

o

 

Connect  a  slave  to  the  centralizer  via  bus  (,  see 
Paragraph 4.6). Turn on the product and program 
it  with  the  external  device  connected  to  the 
centralizer.

 

The  external  device  cannot  be 

connected to a slave device. 

o

 

Repeat  the  previous  step  for  each  slave  in 
possession. 

 

o

 

Use the devices

 

 

After  having  programmed  the  various  devices,  it  is  possible  to 
control  them  with  the  external  device  connected 

only

  to  the 

centralizing  device.  The  slave  devices  are  connected  with  the  bus 
(see Paragraph 4.6) to the centralizing device but are controlled by 
the external device. 
 

 

The devices, if more than one, must be connected one by 

one  and  programmed  one  by  one.  Each  device  has  the  same 
default address. (see Paragraphs 3.2.1, 3.3.2 and 3.4.2) 
 
3.2  –  PROGRAMMING  BY  ELK22DKP  KEYBOARD  (only  for 
ELK22MP e ELK22MPM) 
 
3.2.1 – DESCRIPTION 
 

Only  the  ELK22MP  and  ELK22MPM  models  can  be  programmed 
via  the  ELK22DKP  keypad.  Through  the  bus  connection  (see 
Paragraph  4.6)  it  is  possible  to  program  the  slave  products 
ELK22MPS.  The  keyboard  connected  to  the  ELK22MP  or 
ELK22MPM  model  can  program  and  set  the  parameters  of  each 
ELK22MPS connected via bus. 
 

The default MODBUS address is 100. 
 
 

3.2.2

 - 

FRONT PANEL DESCRIPTION (ELK22DKP)

 

 

1  –  Key 

 

:  Used  to  access  programming  of  the  operating 

parameters and to confirm the selection. 

2 - Key 

 : Used for decreasing setpoint setting, values to be set, 

and  for  parameter  or  module  selection.  Long  pressed  in  full  menu 
programming,  it  changes  the  access  level  of  the  selected 

parameter.  (See  para. 3.1, 3.3).  Long  pressed in  the  menu  for  the 
module selection performs the download of the parameters from the 
module to the programming keypad. (See para. 3.5). 

3  -  Key 

  :  Used for  increasing setpoint setting, values  to be set, 

and  for  parameter  or  module  selection.  Long  pressed  in  full  menu 
programming,  it  changes  the  access  level  of  the  selected 
parameter.  (See  para. 3.1, 3.3).  Long  pressed in  the  menu  for  the 
module  selection  performs  the  upload  of  the  parameters  from  the 
programming keypad to the module. (See para. 3.5). 

4  –  Key 

:  When  in  programming  mode,  you  can  use  it  to  quit 

programming  or  to  cancel  the  change  of  a  parameter.  During 
normal operation, it enables the menu to select a module. 

5  –  4  red  digits: 

Process  value  during  operation,  parameter 

selected during programming. 

6

 

–  4  green  digits: 

Setpoint  value  during  operation,  value  of  the 

parameter selected during programming. 

7  –  LED  1 

:  It  indicates  OUT1  output  status.

  LED  2 

:  It  indicates 

OUT2 output status.

 

8 – LED AL 

: It indicates the state of the alarm. 

9  –  LED  B1 

:  In  full  programming  mode,  it  indicates  that  the 

parameter  is  not  visible  in  the  operator  menu. 

LED  B2 

:  In  full 

programming mode, it indicates that the parameter is visible in the 
operator menu. 

10 – LED °C 

: It indicates unit of measure in degrees centigrade.

  

11  –  LED  °F 

:  It  indicates  measurement  units  in  degrees 

Fahrenheit. 

12 – LED REM 

: In parameters programming mode, it indicates that 

you  are  changing  the  selected  parameter.  In  module  selection 
programming  mode,  it    indicates  that  you  are  selecting  a  remote 
module. 

13  –  Led  MAN

  :  In  module  programming  mode,  it  indicates  the 

download of a setting. 

 
 
3.2.3- MODULE SELECTION 

Pressing the button 

 

lights up the 

REM

 LED to indicate that you 

can select on which ELK22MP you want to connect to and interact 
with  the  programming  keypad..  The  4-color  display  displays  the 
read  temperature  while  the  4-screen  green  display  shows  the 
address  of  the  ELK22MP  you  are  currently  selecting.  Use  the 

 

and 

  keys  to  select  the  desired  ELK22MP  depending  on  the 

address you set. Pressing the key 

 

confirms the selection of the 

ELK22MP with the displayed address. 
 

3.2.4 - SETPOINTS FAST SETTING 

The  4  green  displays  display  always  displays  the  setpoint  set. 
Pressing  the 

  key  increases  the  value  and  pressing  the 

  key 

decreases  the  value.

 

These  keys  act  at  one-digit  steps,  but  if 

pressed  for  more  than  half  a  second,  the  value  increases  or 
decreases  rapidly  to  allow  quick  access  to  the  desired  value.  The 
setpoint can be set with a value between the value programmed in 
para.

 “SSP”

 and the value programmed in para. 

“FSP”.

  

 

3.2.5 - PROGRAMMING THE PARAMETERS

 

To  have  access  to  the  operating  parameters  of  the  device  in  the 
installer  mode,  you  must  press  the  key 

  and  hold  it  for  about  2 

seconds,  while  pressing  the  key 

  for  user  mode  access.  The 

display  will  show 

“SET”

  and  then 

“PASS”

  if  a  password  for  the 

installer  access  is  set.  Use  the 

  and 

  keys  to  enter  the 

password and confirm with 

. The red display shows the code that 

identifies the parameter, the green display shows the value set and 
with  the 

  and 

  keys you  can select  the  parameter  you want  to 

edit.  Once  the  desired  parameter  is  selected  by  pressing  the  key 

, the 

“REM”

 LED lights up to indicate that you are changing the 

parameter setting using the 

 

and

 

 keys. After setting the desired 

value,  press  again  the  key 

;  the  new  value  will  be  stored  while, 

pressing  the  key 

,  the  new  value  will  not  be  stored,  then  the 

“REM” 

LED  will  switch  off.  By  using  the 

  and 

  keys,  you  can 

select  another  parameter  and  change  it  as  described.  To  exit  the 
programming mode, do not press any key for about 10 seconds if in 
user mode or 20 seconds if in the installer mode, or hold down the 

key 

 

until you exit the programming mode. 

Summary of Contents for ELK22MP

Page 1: ...1 For normalized signals 4 20mA 0 10V It is designed for mounting on a din rail The ELK22MP series consists of 4 models 3 of these act as a centralizer and one of them as a slave The models of the ELK...

Page 2: ...he menu to select a module 5 4 red digits Process value during operation parameter selected during programming 6 4 green digits Setpoint value during operation value of the parameter selected during p...

Page 3: ...munication speeds adopted range from 1200 to 38400 baudrates and allow very satisfactory performances while remaining well below the limits imposed by the RS485 standard This allows the line to be wir...

Page 4: ...ters of the instrument can be read and written via serial communication The configurable parameters are found in Paragraph 6 4 WARNINGS FOR INSTALLATION AND USE 4 1 PERMITTED USE The device has been d...

Page 5: ...and a maximum of 1 to 31 slave devices A devices sequence that have ELK22MPM or ELK22MP as a centralizer must consist of a centralizer device and a maximum of 1 to 15 slave devices Two control units...

Page 6: ...must be the device to which the line is connected that must have the termination resistor To do this disconnect the resistance from the accessory and continue the line with the cables for RS485 as bel...

Page 7: ...programming the parameter Cont ON FN the parameter OxF H REG the parameter OyF C REG The adjustment operation operates on outputs depending on the measurement of the setpoint SP1 and hysteresis HPOS...

Page 8: ...nect one ELK22MP at time and set the ADR parameter before connect the next ELK22MP Example connect and power up the first ELK22MP program the ADR parameter to 0 and power off the system Connect the se...

Page 9: ...6 LHdo None 0x19 25 AL2 Alarm threshold SSP FSP 0 0x1A 26 HAL2 Hysteresis of alarm remedy 0 100 1 0x1B 27 AL2D Delay of alarm remedy 0 100 0 sec 0 0x1C 28 ADR Module address 1 16 16 0x1D 29 For each m...

Page 10: ...LSB byte 0 byte1 0x06 byte 2 byte 3 byte 4 byte 5 byte 6 byte 7 7 4 FUNCTION 7 READ ALLARM STATUS The request has the following frame Slave number Function number CRC LSB MSB byte 0 byte1 0x07 byte 6...

Page 11: ...the following frame Slave number Function number First word address MSB LSB Value to write MSB LSB byte 0 byte1 0x06 byte 2 byte 3 byte 4 byte 5 The normal reply is merely an echo of the request messa...

Page 12: ...ay outputs and front reinforced between low voltage parts 24 and 240 power supply and relay outputs and low voltage parts static inputs and outputs reinforced between power supply and relay outputs re...

Page 13: ...ption of the probe Check that the probe is correctly connected to the device and then verify that the probe is working properly 11 2 CLEANING It is recommended to clean the device only with a slightly...

Reviews: