EL.CO. S.R.L.  – ELK22MP

 

INSTRUCTIONS FOR USE 

- Ver.05 - 03/22 - PAG. 5 

the  cables  for  the  input  sensors  are  kept  away  from  power  cords 
and  other  power  cables,  in  order  to  avoid  induction  of 
electromagnetic  disturbances.  Output  SSRs  and  inputs  are  not 
electrically insulated. Connect on the input only insulated probes. If 
some  wiring  harness  cables  are  shielded,  it  is  recommended  to 
connect them to one side on the ground. Finally, it is recommended 
to check that the set parameters are the desired ones and that the 
application  works  properly  before  connecting  the  outputs  to  the 
actuators  in  order  to  avoid  system  abnormalities  that  could  cause 
damage to persons, things or animals.  

 

 
4.4 – ELECTRICAL SCHEME CONNECTIONS 
 
4.4.1 - ELK22MPS 

 

 

 

4.4.2 - ELK22MPE 

 

 

 
 
4.4.3 - ELK22MP e ELK22MPM 

 

 

 
 
 

4.4  -  ELECTRICAL  SCHEME  CONNECTIONS  FOR  ELK22DKP 
(only for ELK22MP or ELK22MPM) 
 

                    

 

 

4.5 – CONNECTION FROM ONE DEVICE TO ANOTHER DEVICE 
 

The  ELK22MP  series  devices  can  be  connected  to  each  other  via 
the bus connector supplied as an accessory. (see Paragraph 10.6). 
Slave devices must be connected to a centralization device to form 
a sequence. 

 

  A  devices  sequence  that  have  ELK22MPE  as  a  centralizer 

must consist of a centralizer device and a maximum of 1 to 31 slave 
devices.

 

 

A devices sequence that have ELK22MPM or ELK22MP as a 

centralizer must consist of a centralizer device and a maximum of 1 
to 15 slave devices. 

 

Two  control  units  cannot  be  connected  to  each  other  via  the 

bus  but  must  be  considered  as  two  distinct  devices.  Two  control 
units  connected  to  each  other  via  bus  can  cause  a  malfunction  of 
the product. 
 

Be careful if you change the centralization device. If you switch 

from an ELK22MPE to an ELK22MPM or ELK22MP centralizer, pay 
attention to the number of ELK22MPS connected via bus.

 

 
 

4.6 – CONNECTION WITH TERMINAL RESISTOR 

 
ELK22MP  devices  use  RS485  via  bus  to  communicate  with  each 
other.  In  particular,  the  centralizing  device  communicates  via  bus 
with the slave devices in order to program them. 
The  RS485  line  requires  a  termination  resistor  to  avoid 
disturbances. This resistance, 120 Ohm, must be placed at the end 
of an RS485 line. Through the connector (see paragraph 10.6) it is 
possible to mount the termination resistor directly on the bus at the 
end of the ELK22MP series device line. 
 

 

The  termination  resistor  is  mandatory  for  the  operation 

of any RS485 line. 
 
Terminating  a  line  of  ELK22MP  series  devices  with  the 
connector (see Paragraph 10.6) and the 120 Ohm resistor gives 
the possibility to terminate an RS485 serial line. The accessory 
is already supplied with a 120Ohm resistor. 
 
 

 

Resistor 120 Ohm 

Summary of Contents for ELK22MP

Page 1: ...1 For normalized signals 4 20mA 0 10V It is designed for mounting on a din rail The ELK22MP series consists of 4 models 3 of these act as a centralizer and one of them as a slave The models of the ELK...

Page 2: ...he menu to select a module 5 4 red digits Process value during operation parameter selected during programming 6 4 green digits Setpoint value during operation value of the parameter selected during p...

Page 3: ...munication speeds adopted range from 1200 to 38400 baudrates and allow very satisfactory performances while remaining well below the limits imposed by the RS485 standard This allows the line to be wir...

Page 4: ...ters of the instrument can be read and written via serial communication The configurable parameters are found in Paragraph 6 4 WARNINGS FOR INSTALLATION AND USE 4 1 PERMITTED USE The device has been d...

Page 5: ...and a maximum of 1 to 31 slave devices A devices sequence that have ELK22MPM or ELK22MP as a centralizer must consist of a centralizer device and a maximum of 1 to 15 slave devices Two control units...

Page 6: ...must be the device to which the line is connected that must have the termination resistor To do this disconnect the resistance from the accessory and continue the line with the cables for RS485 as bel...

Page 7: ...programming the parameter Cont ON FN the parameter OxF H REG the parameter OyF C REG The adjustment operation operates on outputs depending on the measurement of the setpoint SP1 and hysteresis HPOS...

Page 8: ...nect one ELK22MP at time and set the ADR parameter before connect the next ELK22MP Example connect and power up the first ELK22MP program the ADR parameter to 0 and power off the system Connect the se...

Page 9: ...6 LHdo None 0x19 25 AL2 Alarm threshold SSP FSP 0 0x1A 26 HAL2 Hysteresis of alarm remedy 0 100 1 0x1B 27 AL2D Delay of alarm remedy 0 100 0 sec 0 0x1C 28 ADR Module address 1 16 16 0x1D 29 For each m...

Page 10: ...LSB byte 0 byte1 0x06 byte 2 byte 3 byte 4 byte 5 byte 6 byte 7 7 4 FUNCTION 7 READ ALLARM STATUS The request has the following frame Slave number Function number CRC LSB MSB byte 0 byte1 0x07 byte 6...

Page 11: ...the following frame Slave number Function number First word address MSB LSB Value to write MSB LSB byte 0 byte1 0x06 byte 2 byte 3 byte 4 byte 5 The normal reply is merely an echo of the request messa...

Page 12: ...ay outputs and front reinforced between low voltage parts 24 and 240 power supply and relay outputs and low voltage parts static inputs and outputs reinforced between power supply and relay outputs re...

Page 13: ...ption of the probe Check that the probe is correctly connected to the device and then verify that the probe is working properly 11 2 CLEANING It is recommended to clean the device only with a slightly...

Reviews: