elco ELK 38 Operating Instructions Manual Download Page 13

ELCO S.r.l. - ELK 38 - OPERATING INSTRUCTIONS - Vr. 02 - ISTR 06261 - PAG. 13

 

Usrb – KEY U FUNCTION : Decides which function is associated to 
key U. The possible selections are : 
= noF : no function 
= tunE : Pushing the key for 1 sec. at least, it is possible to 
activate/deactivate the Auto-tuning or the Self-tuning 
= OPLO : Pushing the key for 1 sec. at least, it is possible to swap 
from the automatic control (rEG) to the manual one (OPLO) and vice 
versa. 
= Aac : Pushing the key for 1 sec. at least, it is possible to 
acknowledge the alarm.  
= ASi : Pushing the key for 1 sec. at least, it is possible to 
acknowledge an active alarm  
 = CHSP : Pushing the key for 1 sec. at least, it is possible to select 
one of the 4 pre-programmed Set Points on rotation.  
= OFF : Pushing the key for 1 sec. at least, it is possible to swap 
from the automatic control (rEG) to the OFF control (OFF) and vice 
versa. 
diSP  -  VARIABLE  VISUALISED  ON  THE  DISPLAY:    Parameter 
through  which  it  is  possible  to  decide  what  is  visualised  on  the 
display : the process variable (= dEF), the control power (= Pou), the 
active Set Point (= SP.F), the Set Point active when there are ramps 
(= SP.o) or the alarm threshold AL1 (= AL1). 
AdE - 
SHIFT VALUE FOR THE SHIFT INDEX FUNCTIONING: This 
allows one to decide the functioning mode of the 3 led shift indexes. 
The  lighting  of  the  green  led  “=” indicates that the process value is 
within the range [SP+AdE ... SP-AdE], the lighting of the red led “-” 
indicates  that  the  process  value  is  lower  than  the  value  [SP-AdE] 
and the lighting of the red led “+”indicates that the process value is 
higher than the value [SP+AdE]. 
Edit  -  FAST  PROGRAMMING  OF  ACTIVE  SET  POINT  AND 
ALARMS: This decides which are the Sets that can be programmed 
by the fast procedure. The parameter can be programmed as : 
=SE:  The  active  Set  Point  can  be  modified  while  the  alarm 
thresholds cannot be modified 
=AE :The  active  Set  Point  cannot  be  modified  while  the  alarm 
thresholds can be modified 
=SAE:  If  the  active  Set  Point  or  the  alarm  thresholds  can  be 
modified 
=SAnE:  If  the  active  Set  Point  or  the  alarm  thresholds  cannot  be 
modified 
 

6 - PROBLEMS, MAINTENANCE AND GUARANTEE 

 
6.1 - ERROR SIGNALLING
 

Error 

Reason 

Action  

- - - - 

Probe interrupted 

Verify 

the 

correct 

connection 

between 

probe  and  instrument  and 
then  verify  the  correct 
functioning of the probe 

uuuu 

The  measured  variable 
is  under  the  probe’s 
limits (under-range) 

oooo 

The  measured  variable 
is  over    the  probe’s 
limits   (over-range) 

ErAt 

Auto-tuning 

not 

possible  because  the 
process  value  is  higher 
(with 

“Func” 

=HEAt) 

than  [SP-  |SP/2|]  or 
lower 

(with 

“Func” 

=CooL) 

than 

[SP+ 

|SP/2|]. 

Swap  the  instrument  to 
OFF  control  (OFF)  and 
then  to  automatic  control 
(rEG) in order to make the 
error message disappear. 
Once  the  error  has  been 
found,  try  to  repeat    the 
auto-tuning. 

noAt 

Auto-tuning not finished 
within 12 hours 

Check  the  functioning  of 
probe    and  actuator  and 
try  to  repeat  the  auto-
tuning. 

LbA 

Loop control interrupted 
(Loop break alarm) 

Check  the  working  of 
probe    and  actuator  and 
swap  the  instrument  to 
(rEG) control  

ErEP 

Possible anomaly of the 
EEPROM memory 

Push key “P” 

In  error  conditions,  the  instrument  provides  an  output  power  as 
programmed  on  par  “OPE”  and  activates  the  desired  alarms,  if  the 
relative parameters “ALni” have been programmed = yES. 

 
6.2 - CLEANING 
We recommend  cleaning of the instrument with a slightly wet cloth 
using  water  and  not  abrasive  cleaners  or  solvents  which  may 
damage the instrument. 
 
6.3 - GUARANTEE AND REPAIRS
 
The  instrument  is  under  warranty  against  manufacturing  flaws  or 
faulty material, that are found within 12 months from delivery date.  
The  guarantee  is  limited  to  repairs  or  to  the  replacement  of  the 
instrument.  
The eventual opening of the housing, the violation of the instrument 
or  the  improper  use  and  installation  of  the  product  will  bring  about 
the immediate withdrawal of the warranty’s effects.  
In  the  event  of  a  faulty  instrument,  either  within  the  period  of 
warranty,  or  further  to  its  expiry,  please  contact  our  sales 
department to obtain  authorisation for sending the instrument to our 
company.  
The  faulty  product  must  be  shipped  to  ELCO  with  a  detailed 
description of the faults found, without any fees or charge for ELCO, 
except in the event of alternative agreements. 
 

7 - TECHNICAL DATA 

 
7.1 – ELECTRICAL DATA 
Power supply: 12 VAC/VDC, 24, 115, 230 VAC, 24 VAC/VDC, 100.. 
240 VAC +/- 10% 
Frequency AC: 50/60 Hz 
Power consumption: 4 VA approx. 
Input/s:  1  input  for  temperature  probes:  tc  J,K,S  ;  infrared  sensors 
ELCO IRS J e K; RTD Pt 100 IEC; PTC KTY 81-121  (990

 Ω

 @ 25 

°C); NTC 103AT-2 (10K

 @ 25 °C)  or mV  signals 0...50 mV, 0...60 

mV, 12 ...60 mV or normalized signals 0/4...20 mA, 0..1 V, 0/1...5 V 
, 0/2...10 V. 
Normalized signals input impedance:  0/4..20 mA: 51 

;  mV and V: 

1 M

 

Output/s:  Up  to  2  outputs.  Relay  SPDT  (8  A-AC1,  3  A-AC3  /  250 
VAC) ; or in tension to drive SSR (8mA/ 8VDC). 
Auxiliary supply output: 12 VDC / 20 mA Max. 
Electrical life for relay outputs: 100000 operat. 
Installation category:  II 
Measurement category:  I 
Protection class against electric shock:  Class II  for Front panel 
Insulation:  
Reinforced  insulation  between  the  low  voltage  part  (power  supply 
115  or  230  V  and  relay  outputs)  and  front  panel;  Reinforced 
insulation between the low voltage section (Supply 115 or 230 V and 
relay  outputs)  and  the  extra  low  voltage  section  (input,  SSR 
outputs); Reinforced between power supply and relay; No insulation 
between  supply  12  V  and  input.  No  insulation  between  input  and 
SSR outputs. 
 
7.2 – MECHANICAL DATA
 
Housing: Self-extinguishing plastic, UL 94 V0 
Dimensions: 33 x 75 mm, depth 64 mm 
Weight: 180 g approx. 
Mounting: Flush in panel in 29 x 71  mm hole 
Connections:  2,5 mm

2

 screw terminals block 

Degree  of  front  panel  protection  :  IP  65  mounted  in  panel  with 
gasket 
Pollution situation: 2 
Operating temperature:  0 ... 50 °C 
Operating humidity: 30 ... 95 RH% without condensation 
Storage temperature: -10 ... +60 °C 
 
 
 
 
 
 
 
7.3  –  MECHANICAL  DIMENSIONS,  PANEL  CUT-OUT  AND 
MOUNTING [mm]
 

Summary of Contents for ELK 38

Page 1: ...ACTION PID CONTROL 4 6 DOUBLE ACTION PID CONTROL 4 7 AUTO TUNING AND SELF TUNING FUNCTIONS 4 8 REACHING OF SET POINT AT CONTROLLED SPEED AND AUTOMATIC COMMUTATION BETWEEN TWO SET POINTS 4 9 SOFT STAR...

Page 2: ...er two seconds in the same condition the changing speed increases in order to allow the desired value to be reached rapidly Once the desired value has been reached by pushing key P it is possible to e...

Page 3: ...of the controller During automatic control it is possible to visualize the control power on the display by pushing key UP The range of the power values goes from H100 100 of the output power with rev...

Page 4: ...nearization J Ir J or K Ir CA for thermoresistances Pt100 IEC Pt1 or thermistors PTC KTY81 121 Ptc or NTC 103AT 2 ntc for normalised signals in current 0 20 mA 0 20 or 4 20 mA 4 20 for normalised sign...

Page 5: ...value SP HSEt Vice versa in case of direct action or cooling Func CooL it deactivates the output when the process value reaches SP HSEt in case of symmetrical hysteresis or SP in case of asymmetrical...

Page 6: ...control monitoring and the continuous calculation of the parameters during control Both functions automatically calculate the following parameters Pb Proportional Band tcr1 Cycle time of the output 1r...

Page 7: ...on only works through PID control and allows the limitation of control power when the instrument is switched on for a programmable period of time This is useful when the actuator driven by the instrum...

Page 8: ...ument is in alarm condition the alarm is not activated It will be activated only when the process value is in non alarm conditions and then back in alarm conditions ALARM DELAY the alarm output may be...

Page 9: ...CONFIGURATION BY KEY01 The instrument is equipped with a connector that allows the transfer from and toward the instrument of the functioning parameters through the device ELCO KEY01 with 5 poles conn...

Page 10: ...arm AL1L 9999 9999 27 HAL1 Alarm AL1 hysteresis OFF 9999 1 28 AL1d Activation delay of alarm AL1 OFF 9999 sec OFF 29 AL1i Alarm AL1 activation in case of measuring error no yES no Group LbA parameters...

Page 11: ...defines the error conditions of the input allowing the instrument to give the power programmed on par OPE as output The possibilities are Or the condition occurs in case of over range or probe breakag...

Page 12: ...with Func HEAt than SP SP 2 or higher with Func CooL than SP SP 2 OFF Autotuning disabled When it s occurring an Autotuning cycle led AT blinks SELF SELF TUNING ENABLE Parameter used to enable yES or...

Page 13: ...y to repeat the auto tuning LbA Loop control interrupted Loop break alarm Check the working of probe and actuator and swap the instrument to rEG control ErEP Possible anomaly of the EEPROM memory Push...

Page 14: ...C 58 0 230 0 F 0 20 mA SEnS 0 20 1999 9999 199 9 999 9 19 99 99 99 1 999 9 999 4 20 mA SEnS 4 20 1999 9999 199 9 999 9 19 99 99 99 1 999 9 999 0 50 mV SEnS 0 50 1999 9999 199 9 999 9 19 99 99 99 1 99...

Reviews: