![elco Combi 24 Operating Manual Download Page 9](http://html1.mh-extra.com/html/elco/combi-24/combi-24_operating-manual_2377072009.webp)
9
Product description
Technical data for THISION S PLUS
Type THISION S PLUS
Combi 24
Combi 34
Permit
Category
SVGW number
CE0063BQ3021
BE-I2E(S), I3P
Heat exchanger type
OSS2
OSS2
Output
G20
Full load
80/60°C
kW
22,1
33,6
40/30°C
kW
24,7
37,3
Low load
80/60°C
kW
4,9
4,9
40/30°C
kW
5,3
5,3
G25
Full load
80/60°C
kW
18
27,3
Low load
80/60°C
kW
4,1
4,1
G31
Full load
80/60°C
kW
22,1
33,6
40/30°C
kW
23,6
35,9
Low load
80/60°C
kW
15,8
15,8
40/30°C
kW
17,6
17,6
DHW flow (according to EN 625)
l/min.
10,7
13,3
Input
G20
Full load
kW
22,5
34,2
Low load
kW
5
5
G25
Full load
kW
18,4
27
Low load
kW
4,2
4,2
G31
Full load
kW
22,5
34,2
Low load
kW
16
16
Boiler efficiency
Full load
80/60°C
%
98,2
98,2
Low load
40/30°C
%
109,7
109,1
Gas type
Natural gas or propane gas
CO
2
natural gas
min./max.
Vol. %
8,8 / 9,2
CO
2
propane gas
min./max.
Vol. %
10,5
O
2
natural gas
min./max.
Vol. %
4,6 / 5,4
NOx annual emissions value
(3%O
2
)
mg/m
3
15
11
CO annual emissions value
(3%O
2
)
mg/m
3
15
22
Standby losses
Tk 70°C
W
60
60
Max. flue gas temperature
80/60°C
68
69
Mass flow of flue gas
max.
g/s
14,4
15,6
Overpressure at boiler output
max.
Pa
75
75
Water volume in heating circuit
l
5
5
Water volume DHW circuit
l
14
25
Weight
kg
73
84
Gas flow pressure - standard
mbar
20
Gas flow-pressure min./max.
mbar
17 / 25
Operating pressure of heating unit
min./max.
bar
1 / 3
DHW operating pressure
min./max.
bar
1 / 8
DHW operating temperature
max
°C
60
Content/pre-pressure of expansion vessel
l / bar
12 / 1
-
Voltage/frequency
min./max.
Volt/Hz
230 / 50
Boiler power consumption
W
77
98
Pump power consumption
min./max.
W
12 / 35
12 / 56
Width / depth / height
mm
840 x 385 x 680
External thread of gas connection
R
3/4”
3/4”
Flow/return external thread
R
1”
1”
Flue gas connection PPS
Diameter
DN
80
80
Outdoor air connection
Internal
Ø mm
125
125
Condensate connection PVC
External
Ø mm
24
24
Product characteristics, for calculating the system consumption value according to DIN V4701-10:
Nominal heat output
Qn (kW)
22,1
33,6
Efficiency level at nominal heat output
η100% (%)
98,2
98,2
Partial load efficiency level
η30% (%)
109,7
109,1
return temperature, when measuring at 30% partial load efficiency level
T 30% (°C)
30
30
Standby heat loss
q B,70 (%)
0,27
0,18
Auxiliary energy: Boiler incl. integrated heating circuit pump
PHE (W)
77
98