Parameters technician
Menu
Line no.
Selection possibilities
Unit
Min.
Max
Factory setting
Configuration
6051
Voltage value 2 H2 module 1
V
0
10
0
6059
Voltage value 2 H2 module 2
V
0
6067
Voltage value 2 H2 module 3
V
0
6052
Function value 2 H2 module 1
-
-1000
5000
0
6060
Function value 2 H2 module 2
-
0
6068
Function value 2 H2 module 3
-
0
6097
Sensor type collector
-
NTC, PT 1000
NTC
6098
Readjustm collector sensor
°C
-20
20
0
6100
Readjustm outside sensor
°C
-3
3
0
6110
Time constant building
h
0
50
5
6117
Central setpoint shift
°C
1
100
5
6118
Setpoint reduction delay
K/min
Off , 1 - 200
20
6120
Frost protection plant
-
Off, On
On
6200
Save sensors
-
No, Yes
No
6205
Reset to default parameters
-
No, Yes
No
6212
Check nr heat source 1
-
0
199999
0
6213
Check nr heat source 2
-
0
199999
0
6215
Check nr storage tank
-
0
199999
0
6217
Check nr heating circuits
-
0
199999
0
6220
Software version
-
0
99
0
LPB
6600
Device address
-
0
239
1
6601
Segment address
-
0
16
0
6604
Bus power supply function
-
Off, Automatically
Automatically
6605
Bus power supply state
-
Off, On
On
6610
Display system messages
-
No, Yes
No
6612
Alarm delay
min
2-60 min
10
6620
Action changeover functions
-
Segment, System
Segment
6621
Summer changeover
-
Locally, Centrally
Locally
6623
Optg mode changeover
-
Locally, Centrally
Locally
6624
Manual source lock
-
Off, Automatically
Automatically
6625
DHW assignment
-
Local HCs, All HCs in segment,
All HCs in system
All HCs in system
6632
Note OT limit ext source
-
No, Yes
No
6640
Clock mode
-
Autonomously, Slave without remote setting, Slave
with remote setting, Master
Autonomously
6650
Outside temp source
-
0
239
0