Siphon and condensate tray
- Loosen the front Phillips screw
(4) at the left-hand side of the air
suction damper.
- Remove the siphon (7) and the
siphon insert (8), and then empty
and clean these.
- Loosen the two clamping rods (11
and 12) with a 45° turn (below the
condensate collection tray) by using
a hexagonal key, and then pull
these forward and out.
- By lifting the internal waste gas
pipe (13) out of the condensate
collection tray (14), and by
simultaneously pressing together
the two bulges at the top of the
waste gas pipe, the collection tray
and the internal waste gas pipe
can be disassembled. Check the
disassembled components for
soiling and, if necessary, clean
them.
- Inspect the O-rings and the siphon
beaker, and exchange these in
case of any defect.
- Both components can be cleaned
with a brush and water.
- The O-rings should be lightly
lubricated for an easier insertion.
- If the siphon (10) needs renewal
and it must be completely
exchanged.
7
8
9
10
13
11
12
14
1
2
3
4
OPEN
CLOSED
Assembly is carried out in the reverse
order.
When assembling the condensate tray,
please make sure that the seal fits
tightly all-around.
During assembly, attention must be
paid that the red markings on the
clamping rods stand in a vertical
position.
After completion of the maintenance
works, and in advance of taking the
system back into operation, it must
be checked for leakproofness and a
correct seating of components.
Use a leak-detecting spray, to check
all gas pipes and screw connections
for leakproofness.
An O
2
/ CO
2
check should be carried
out (see pages 53 and 54).