FUNCTION TESTING 

0

The nozzle shall  be  set to a flowrate of  '5  1/min'. 

Automatic  shut-off  and  tightness: 

1.  To  ensure  proper function of the automatic shut-off and tightness of the  nozzle  spout, attach the

EW 22 test adapter onto the  nozzle spout until stop. Pull the lever to dispense medium ( urea solution

or test fluid). lnsert the tip of the spout into the liquid. The nozzle shall shut off automatically.

2.  Then pull  the nozzle spout out of the liquid and  pull  off the EW  22  test adapter.  There should be 

just a few drips after removing the test adapter.

·---

1. 

2. 

  - - - - - -

· - · · - - · - - - - - -

Tightness: 

While dispensing  liquid  pull  off the EW  22 test adapter quickly. The flow shall stop immediately and 

the spout must not drip more than a few drips. 

-    

f ; , :  

__ 

__ 

- - - - - - - - -

Latching  (if permitted, depending on  regional regulations): 

Latch the lever in  the upper position.  lnsert the tip of the spout into the liquid. The nozzle must shut 

off automatically, the lever shall  move back to neutral  position. 

13 

Summary of Contents for ZVA AdBlue LV

Page 1: ...A AdBlue A AdBlue esky Strana...

Page 2: ...2 Pozn mka Ad Blue je registrovan ochrann zna ka spole nosti VDA Mo ovinov roztok je tak zn m jako AUS32 DEF nebo ARLA32...

Page 3: ...dle EN 13012 stejn jako certifikaci ATEX 0 V N mecku je podle po adavk na vodn z kony TRwS 781 povoleno pou it upev ovac ho za zen ZVA AdBlue LV pokud je tankovac pistole vybavena a provozov na s odtr...

Page 4: ...uvnit pistole P ed uveden m do provozu zatla te testovac adapt r EW 22 na v tla n potrub a na doraz aby do lo k p eklenut ochrany proti chybn mu tankov n paliva EW 22 z st v na erpac pistoli a do konc...

Page 5: ...ti sm ru hodinov ch ru i ek Po proveden prav zkontrolujte znovu m ru pr toku P padn lze tak nastavit pr tok p mo na hadicov konektor EA 075 LV nebo SSB 16 LV Za t mto elem oto te ernou clonu EW SK 3 i...

Page 6: ...ouze n kolik zb vaj c ch kapi ek by m lo vyt ct z v tla n ho potrub pot co byl odta en testovac adapt r 2 Odstra te pi ku trysky z kapaliny a odpojte testovac adapt r EW 22 od v tla n ho potrub Pouze...

Page 7: ...nebo v motorov m prostoru Dodr ujte pros m pokyny v robce vozidla Obsluha v dejn pistole je obdobn jako u b n ZVA Pro v dej mus b t v dejn pistole zcela zasunuta do plnic ho hrdla n dr e AdBlue Pot j...

Page 8: ...pad pono te v tla n potrub do kbel ku s teplou vodou abyste rozpustili krystaly Automatick vypnut nefunguje Zatla te testovac adapt r EW 22 na v tla n potrub a na doraz abyste odemkli ochranu proti ch...

Page 9: ...n datum na pistoli nap klad 16 1 tvrtlet roku 2016 Ze z ruky jsou vylou eny tankovac pistole kter byly vystaveny vn j mu opot eben nebo byly pou v ny nevhodn tekutiny a p sady N klady na v m nu a opra...

Page 10: ...OPERATING CONDITIONS ZVA AdBlue LV is suitable for the use with tiller inlets to ISO 22241 5 The nozzle is type approved to EN 13012 and ATEX certified Note The use of the lever latch is not allowed i...

Page 11: ...ressure within the nozzle This is done by overriding the misfilling prevention of the nozzle push the EW 22 test adapter onto the spout until stop EW 22 remains in this position until the end of the f...

Page 12: ...he flowrate again Alternatively the flowrate can also be adjusted at the hose connection EA 075 LV or SSB 16 LV Screw off hose connection Rotate the black orifice with tool EW SK 3 hex key 3 mm The bl...

Page 13: ...hall shut off automatically 2 Then pull the nozzle spout out of the liquid and pull off the EW 22 test adapter There should be just a few drips after removing the test adapter 1 2 Tightness While disp...

Page 14: ...e boot trunk or the angine bay Please follow your vehicle manufacturer s AdBlue refilling instructions Handling of the nozzle is similar t o conventional ZVA nozzles ln orderto dispense the nozzle mus...

Page 15: ...pter over the nozzle spout to override the misfilling prevention check if the flow rate is at minimum 3 I min when the lever is fully pulled and afterwards in the upper latched position If necessary f...

Page 16: ...elivery date cannot be established the date code on the nozzle e g 2016 means 1st quarter 2016 prevails Excluded are nozzles and parts subject to wear and tear abuse and to contamination Furthermore e...

Reviews: