Page 46 of 78
12.16.
INPUT FUNCTION: VENTING CLOSE
Control of actuators responsible for opening smoke
dampers, windows for venting.
12.17.
INPUT FUNCTION: DRIVE START TEST
Checking the operating capacity of smoke damper
actuators.
12.18.
INPUT FUNCTION: POWER FAILURE
This input is presented as a power failure, e.g. from an
external power supply.
12.19.
INPUT FUNCTION: LIMIT SWITCH
Damper terminals, e.g. damper open/close sensors, are
connected to this input.
Fig. 37 Limit switch input diagram
Resistance values:
1k – closed
2k2 – open
3k2 – intermediate position
12.20.
INPUT FUNCTION: LIMIT SWITCH
GROUP
Damper terminals, e.g. damper open/close sensors, are
connected to this input.
Fig. 38 Limit switch group input diagram
Resistance values:
3k2 – closed,
2k2 – open,
1k – intermediate position
12.21.
INPUT FUNCTION: MANUAL CONTROL
In manual control, the unit stops responding to automatic
alarms from the fire alarm control panel (a fire reset occurs,
switching the appliances to idle mode).
12.22.
INPUT FUNCTION: MANUAL FIRE
ALARM
Manual input of a fire alarm from FACP, for example using
the control panel.
12.23.
INPUT FUNCTION: SMOKE DETECTOR
ALARM
If an alarm is notified from a smoke detector during a fire, a
fan will be shut down.
If a smoke position is set for a damper, it will switch to that
position at this alarm.
12.24.
INPUT FUNCTION: SMOKE DETECTOR
WARNING
If a warning is notified from a smoke detector, it will be
indicated but will not cause any change of system operation
control.
12.25.
INPUT FUNCTION: EVACUATION WITH
FIREFIGHTING ACTION
Firefighting action signal input. Active state at this input
indicates that additional relay outputs are operated in
EPSCUS modules.
12.26.
INPUT FUNCTION: GENERAL ALARM
A general purpose input for connecting any external signals
to be displayed by the visualization system.
12.27.
INPUT FUNCTION: PRESSURE
CONTROL
An input forcing control based on pressure and not
temperature measurement results.
12.28.
INPUT FUNCTION: EXTERNAL
TEMPERATURE SENSOR
Temperature measurement, result in degrees Celsius *10.
The result of measurement is responsible for fan action in
the assigned zone.
Summary of Contents for FPM+
Page 1: ...technical and operational documentation Doc version 3 0 100 ...
Page 7: ...Page 6 of 78 Fig 2 Control unit topology diagram ...
Page 32: ...Page 31 of 78 Fig 25 SKC A to control unit and power supply wiring diagram ...
Page 38: ...Page 37 of 78 Fig 29 CP5004 type housing ...
Page 39: ...Page 38 of 78 Fig 30 CP5005 type housing ...
Page 40: ...Page 39 of 78 Fig 31 CP5008 type housing ...
Page 59: ...Strona 58 z 78 ...
Page 61: ...Strona 60 z 78 ...
Page 63: ...Strona 62 z 78 ...
Page 65: ...Strona 64 z 78 ...
Page 67: ...Strona 66 z 78 ...