Page 42 of 78
10.4.
INPUT TYPE: DIGITAL THREE-STATE
Digital three-state inputs are present in LSK and EPSCUS
modules.
Inputs of this type will indicate either of the three states:
open, closed, or intermediate.
It is used for such functions as damper operation, where the
damper status can be verified with the right selection of
resistors.
10.5.
INPUT TYPE: ANALOG RESISTIVE
Analog resistive inputs are present in EPSCUS modules.
They are used to measure the value of connected resistance.
Analog resistive inputs do not trigger alarms.
10.6.
INPUT TYPE: DIGITAL SUPERVISED NO
Digital supervised NO inputs are present in EPSCUS
modules.
A digital supervised NO input is a digital input with line state
monitoring. Monitoring is done via a connected NO contact
that triggers resistor signal.
The resistance values are the following: 3.3kOhm for idle,
1kOhm for alarm.
This input indicates line failure if the line resistance value is
outside these two values.
Fig. 34 Digital supervised NO (2EOL/NO) input diagram
10.7.
INPUT TYPE: DIGITAL SUPERVISED NC
Digital supervised NC inputs are present in EPSCUS
modules.
A digital supervised NC input is a digital input with line state
monitoring. Monitoring is done via a connected NC contact
that triggers resistor signal.
The resistance values are the following: 1kOhm for idle,
3.3kOhm for alarm.
This input indicates line failure if the line resistance value is
outside these two values.
Summary of Contents for FPM+
Page 1: ...technical and operational documentation Doc version 3 0 100 ...
Page 7: ...Page 6 of 78 Fig 2 Control unit topology diagram ...
Page 32: ...Page 31 of 78 Fig 25 SKC A to control unit and power supply wiring diagram ...
Page 38: ...Page 37 of 78 Fig 29 CP5004 type housing ...
Page 39: ...Page 38 of 78 Fig 30 CP5005 type housing ...
Page 40: ...Page 39 of 78 Fig 31 CP5008 type housing ...
Page 59: ...Strona 58 z 78 ...
Page 61: ...Strona 60 z 78 ...
Page 63: ...Strona 62 z 78 ...
Page 65: ...Strona 64 z 78 ...
Page 67: ...Strona 66 z 78 ...