12. TRANSMITTER CONFIGURATION VIA SOFTWARE
The transmitter can be fully programmed by using BrowserOne v. 3.4.7 or higher with the module for the control unit v.
8.4.11 or higher. The control unit firmware must be 8.2.0.0 or higher.
See the specific technical documentation for information on other expressly compatible control unit models.
Perform the following operations:
• Start the connection as explained in the programming manual of the control unit.
• Read the current configuration, open the “
Zones
” page and identify the number of the zone that is assigned the
acquired code of the transmitter.
• Still in the Zones page, open the “
Radio devices NG-TRX
” tab.
On the side of the page concerning the NG-TRX wireless devices, some useful notes are displayed for the correct
configuration of the detector, depending on the selection of the “
Supervision interval
” and the “
Tx Boost
” function.
In the bottom page you can find the specific section for the transmitter channels configuration, described in chapter “10.
ELECTRICAL CONNECTIONS”.
Event type for each channel.
Press to delete the acquired code.
The picture highlights the
informations concerning the
radio NG-TRX system, the
firmware version and the
transmitter model.
Activates the internal buzzer of the transmitter in
alarm or reset for a local operation check of all
channels (unless differently set for each single
channel).
Default
: disabled (any anomaly is
signalled in any case).
Function available only if you set a precise
supervision interval; it allows you to delay the
anomaly signal generated by the “supervision
failure” signal.
Select to increase the power of the RF section.
WARNING: this causes a decrease in battery duration.
Use only when the range is not
sufficient.
You can choose between “
Automatic
”, “
Minimum
consumption
” to maximize battery life when the
signal reception is sufficient, “
Maximum power
”
in case of high limitations due to adverse site
conditions (drawback: battery life reduction).
Default
: Automatic.
Set the periodic transmission cadence necessary
for the control unit to detect the transmitter control
failure, with the consequent reporting and alert
actions settable from other software pages.
Setting a short interval will affect the battery
duration of the device. In the Default condition, the
general parameters will be used: they are set in the
“System options” page for the NG-TRX devices.