SURFACE MOUNT LEDFIRE III EMERGENCY INSTALLATION INSTRUCTIONS
DRAFT
19. self-test inDicator leDs
20. SELF-tESt/ COMMISSIONING INtERVAL PROGRAMMING
The table below shows the operation of the Surface Mount Ledfire III status indicators:
The self-test mode must first be enabled to perform tests. This is done by switching the breaker in the correct
sequence as illustrated below. The same sequence can also be used with the test button on a single device.
The test interval is fixed and set to 26 weeks / 182 days. The LEDs indicate the status of the device and which
functions are being performed. For more information refer to the
Configurations: Status LEDs and Device
Modes
document.
INDICATOR
DESCRIPTION
YELLOW
2sec ON / 2sec OFF
YELLOW
4sec ON / 1sec OFF
YELLOW
0.5sec ON / 0.5sec OFF
GREEN
1xFlash
Device is performing a duration test
Last duration test passed. The duration
was met when last run. Test ran less
than five days ago
Last duration test failed. Failed to meet
duration. The device is not currently
running a new test. Mains is on
A duration test is pending. The device
is not in any self-test and set to
normal mode
10
3X SwITCH CyCLES
wAIT & REPEAT
WAIT 5 sec.
then repeat the
3X SWITCH CYCLE
NOTE:
If the wait in-between breaker or test button push sequences is longer than
30 seconds
then it will timeout and the procedure will need to begin again.
5 sec.
OFF
ON
OFF
ON
OFF
ON
5 sec.