background image

 

EK-WL8-SND/AU 

WIRELESS SOUNDER  

STFV.425412.001-AU-UM rev. 20

 

20.07.2021 

Page 5 from 8 

 

INDICATION 

The device has a LED which indicates its state according to the following:

 

 

 

 

 

 

 

 

TESTING 

To test the device, activate an alarm condition on the system via a call-point or fire 
sensor. The sounder should activate with the selected tone and volume. 

To stop the test silence and reset the control panel. 

АNALOG DATA 

The device provides the translator module with analog data about air temperature 
and  voltage  levels  on  its  batteries.  This  information  can  be  viewed  in  the  “Ekho 
Configiurator

” software. 

 

By  analyzing  the  voltage  levels,  you  can  manage  maintenance  procedures  and 
predict when you will have to replace the batteries. 

WARNINGS & LIMITATIONS 

Devices use high quality electronic components and plastic materials that are highly 
resistant  to  environmental  deterioration.  However,  after  10  years  continuous 
operation it is advisable to replace them to reduce the risk of reduced performance 
caused  by  external  factors.  Ensure  the  devices  are  only  used  with  compatible 
control panels. Detection systems must be checked, serviced and maintained on a 
regular basis to confirm correct operation.  

Refer to and follow National Codes of Practice and other internationally recognized 
fire  engineering  standards.  Appropriate  Risk  Assessment  should  be  carried  out 
initially to determine correct design criteria and updated periodically. 

 

 

LED indication 

Device’s state 

No indication or green flashes  

Standby mode 

Yellow flashes every 4 seconds 

Fault state 

– low battery  

Frequent red flickering 

Device is activated 

Summary of Contents for EK-WL8-SND/AU

Page 1: ...he wireless wall sounder via the connected translator expander modules This wall sounder has 4 selectable tones and the volume can be adjusted The device is supplied with a mounting kit The product co...

Page 2: ...type CR123A 2 75 3 2V 3 months after primary battery low fault Dimensions with the base 108 mm x 108 mm x97 mm Max tolerated humidity no condensing 95 RH Operating temperature range From 10 C to 55 C...

Page 3: ...to the wall using screws the sounder can then be clipped onto the back box Preferably the device should be installed away from metallic objects doors and power lines as they can cause the communicatio...

Page 4: ...n 500ms Off ON 1 Dual tone 990Hz 650Hz 250ms 250ms 1 ON Continuous tone 990Hz 1 1 Pulsed tone synchronized 990Hz 1s On 1s Off NOTE Please refer to picture showing the DIP switch orientation The sounde...

Page 5: ...lace the batteries WARNINGS LIMITATIONS Devices use high quality electronic components and plastic materials that are highly resistant to environmental deterioration However after 10 years continuous...

Page 6: ...years of operation regardless of their indicated discharge level To replace the batteries use Panasonic CR123A primary and secondary batteries or other with similar characteristics The batteries must...

Page 7: ...SOUNDER STFV 425412 001 AU UM rev 20 20 07 2021 Page 7 from 8 Angle Minimal sound pressure dB A for all supply voltages at 1 m Horizontal and vertical orientation 15 80 45 88 75 93 105 93 135 88 165...

Page 8: ...07 2021 Page 8 from 8 SAI Global ABN No Lic SMK 41078 67 153 750 648 Hochiki Australia Pty Ltd Block Y Unit 1 Regents Park Estate 391 Park Rd Regents Park NSW 2143 Australia Telephone 61 2 9738 5566...

Reviews: