2. Quick Start
TEC 2000 Installation & Operation Manual E2K-405-0902
2-1
2
Quick Start
Quick start provides step-by-step instructions for initializing the TEC 2000 actuator. When these
instructions are complete, the position limits will be set and the actuator will be ready for normal
operation.
NOTE: The actuator has been configured as specified by the customer and no further changes
should be required. If full valve data was not provided when ordered, or if changes are needed, see
Section 5
,
Customizing Actuator Settings
.
X
WARNING: Use caution when working on, with, or around valves and actuators. High
pressures, forces, voltages, and flammable media can be present.
X
WARNING: Verify voltage rating on nameplate before connecting power.
2.1. Set Position Limits
1. Power actuator. The alarm message “
SET LIMITS BEFORE OPERATING
” will be
displayed. The alarm icon and the yellow LED will be flashing. Valve position will be
displayed as “
EE%
.”
2. Proceed as follows to set the limits. See
Section 5.6.3, Set Valve Travel Limits
for
additional details.
A. Enter the “
SETUP
” mode.
1. Place the selector knob in the
STOP
position.
2. Rotate the control knob to
YES
, then
NO
, then
YES
, then
NO
in rapid
succession
and then release. The Setup icon will be displayed on the display module and
“
SETUP?
” will be displayed on the message center.
3. Rotate the control knob to
YES
. “
SET LIMITS BEFORE OPERATING
” will be
displayed on the message center.
4. Rotate the control knob to the
LOCAL
position. The message “
CLOSE VALVE
THEN SELECT STOP
” will be displayed.
B. Set close valve travel limit.
CAUTION: It is recommended the valve be positioned using the handwheel
while setting the limits to prevent valve damage.
1. Valve Operation
1a. For
Electrical Operation
use the control knob to move the valve in the
close direction. Proceed to Step No. 2.
1b. For
Manual Operation
depress the declutch lever while rotating the
handwheel until the clutch is fully engaged. Release the lever. The clutch
will be retained in the handwheel mode by spring-loaded latches. Verify the
valve is fully closed. Move the valve in the open direction for one handwheel
turn to allow for coasting of the motor.
2. When the desired close position is reached, place the selector knob in the
STOP
position. “
ACCEPT CLOSE LIMIT?
” will be displayed.
3. Rotate the control knob to
YES
. “
SELECT LOCAL AND OPEN VALVE
” will be
displayed. The close limit is set.
Summary of Contents for TEC2000
Page 1: ...T TE EC C2 20 00 00 0 EIM CONTROLS E2K 405 0902 Preliminary 9 02 Installation Operation Manual...
Page 4: ...iii...
Page 23: ...3 Installation TEC 2000 Installation Operation Manual E2K 405 0902 3 11...
Page 44: ...4 Operation TEC 2000 Installation Operation Manual E2K 405 0902 4 14 4 7 Event Logger TBD...
Page 85: ......