4. Operation
TEC 2000 Installation & Operation Manual E2K-405-0902
4-5
4.1.5. Multi-Port Valve Status Display Functions
Table 4-3
details the various activities and how each is displayed when operating in the
“
MULTI-PORT VALVE
” mode.
Table 4-3 "Multi-port Valve Status" Display Functions
Display Functions
LEDs
Valve Position
Yellow
Red
Green
Position Bar Graph
Port A
OFF
OFF
ON
Valve rotation displayed
as 0°
Moving from Port A to B or
B to C or C to A
OFF
Blinking
OFF
Flashing in the Open
direction
Rotation increments
Port B
ON
OFF
OFF
Valve rotation displayed as
90
°
Port C
OFF
ON
OFF
Valve rotation is displayed
as 180
°
Moving from Port A to C or
C to B or B to A
OFF
OFF
Blinking
Flashing in the close
direction
Rotation decrements
Alarm – displayed on the
bottom line of the message
center
Blinking
OFF
OFF
Alarm Icon flashes
4.2. Remote Display Module (RDM)
The RDM performs the same functions as the LDM.
NOTE: If the RDM does not receive communication messages from the Central Control
Module (CCM) within 5 seconds after power is applied, the RDM will display the flashing
message “
CCM LINK FAILED
” and all three LEDs will blink. This will also occur if
communication is lost for 5 seconds or more.
4.2.1. RDM Operation with LDM
Two RDMs and an LDM can be connected to one actuator. The operation priority is detailed
in
Table 4-4
.