5. Customizing Actuator Settings
TEC 2000 Installation & Operation Manual E2K-405-0902
5-17
Table 5-3 Relay Output Function List
Function List
LSO (Open
limit)
LOW MAIN BATTERY
OVER TORQUE (Open or
Close)
CLOSE INHIBIT
LSC (Close
limit)
LOCAL
VALVE STALL
LOCAL ESD
LSA
(Intermediate
limit A)
STOP (SS OFF)
VALVE DRIFT (MOVED BY
HANDWHEEL)
ESD ACTIVE
LSB
(Intermediate
limit B)
REMOTE
LOST POWER
LOST ANALOG
OPENING
EFM (Electronics fault
monitor)
MOTOR OVERLOAD
ACTUATOR FAIL
CLOSING
OPEN TORQUE
LOST PHASE
GENERIC (Controlled by
Network)
MOVING
CLOSE TORQUE
OPEN INHIBIT
LOW RTC BATTERY
Relays #6 through #8 are Solid State Output relays. These relays are added when an ACM
card is installed. These outputs cannot be individually configured. The motor “starter” type
selected in the factory setup mode determines the control. See
Table 5-4
.
Table 5-4 Solid State Output Relays Configuration
Relay
Default Function
Alternate
Function
Configure
N.O./N.C.
Configure
Flashing
SSO#6
VFD Open Control
Generic
No
No
SSO#7
VFD Close Control
Generic
No
No
SSO#8
VFD Speed Control
Generic
No
No