3. Installation
TEC 2000 Installation & Operation Manual E2K-405-0902
3-18
3.8.3. Two RDMs (one 24Vdc and one 115/208/220/230 Vac power source)
To use two RDMs with one actuator, connect as detailed in
Table 3-9
.
Table 3-9 Two RDMs Connected to the Actuator
RMD
RDM Terminal
Block Number
Function
TEC 2000
Terminal Block
Number
Cable Type-
Belden or
Equivalent
Line
115/230 Vac 50/60 Hz (+)
-
20AWG or Larger
Neu
0V Common
-
20AWG of Larger
3
RS-485 (+)
21
1
RS-485 (-)
23
RDM #1
2
Shield
24
Belden 9841
6
24 Vdc 9=0
9
5
0V Common
10
Belden
8719
3
RS-485 (+)
21
1
RS-485 (-)
23
RDM #2
2
Shield
24
Belden
9841
Belde
n
8723