Seite/Page 21 von/of 26
UV Flame Detector
Type: FL (Ex) d 07-.-..-..
10/21/2016
3
Date
Version
Betriebsanleitung Nr./
Operating Instructions No.
4.09262.9-1
Sufficient UV radiation (intensity) exists, fire alarm detected.
Data word: Current status UV flame detector (bit 4 set = 1)
Fire alarm
Intensity of the UV radiation
depends on the settings of the evaluation function.
Check that the fire alarm on the central fire alarm system is detected based on
the operating manual of the central fire alarm system.
Reset the fire alarm.
(1) For a continuous alarm, in order to reset via the configured fieldbus
set Reset fire alarm. Functional code: $71send.
(2) For automatic resetting, wait for the time to elapse until the
UV flame detector resets.
Depends on the settings of the evaluation function.
Reset via the configured fieldbus system Reset fire alarm.
Functional code: $71send.
Data word: Current status UV flame detector (bit 4 deleted = 0)
Ready
Ready after resetting?
UV flame detector ready.
Data word: Current status UV flame detector (bit 5 deleted = 0) ready
Data word: Current status UV flame detector (bit 6 deleted = 0)
Ready
Check the operation readiness of the central fire alarm system based on the
operating manual of the central fire alarm system.
FB Master IN
Reg. 0002/Lo
Bit 6 = 0
FB Master IN
Reg. 0002/Lo
Bit 5 = 0
LED
Flashi
ng
FB Master IN
Reg. 0002/Lo
Bit 4 = 0
FB Master IN
Reg. 0002/Lo
Bit 4 = 1
LED