Seite/Page 15 von/of 26
UV Flame Detector
Type: FL (Ex) d 07-.-..-..
10/21/2016
3
Date
Version
Betriebsanleitung Nr./
Operating Instructions No.
4.09262.9-1
5.4. Functions test of the UV flame detector type: FL (Ex) d 07-.-FB-..
Switch on operating voltage.
UV test started.
Only for UV flame detector design type: FL (Ex) d 07-T-..-..
UV test running.
Only for UV flame detector design type: FL (Ex) d 07-T-..-..
UV test completed = OK
for 20 sec. max.
Only for UV flame detector design type: FL (Ex) d 07-T-..-..
UV flame detector ready.
Data word: Current status UV flame detector (bit 5 deleted = 0) ready
Only for UV flame detector design type: FL (Ex) d 07-.-FB-..
Data word: Current status UV flame detector (bit 6 deleted = 0)
Ready
Only for UV flame detector design type: FL (Ex) d 07-.-FB-..
FB Master IN
Reg. 0002/Lo
Bit 6 = 0
FB Master IN
Reg. 0002/Lo
Bit 5 = 0
LED
Flash
LED
LED
Blink
LED
Flash