UV Flame Detector
Type: FL (Ex) d 07-.-..-..
10/21/2016
3
Date
Version
Betriebsanleitung Nr./
Operating Instructions No.
4.09262.9-1
WARNING
UV flame detector not ready type: FL (Ex) d 07-T-RE-.. (Fault)!
+
UV test fault:
e.g. visual pane dirty, UV-Fiber-Optic Cable defective, UV - Transmitter
defective.
(1) Clean visual pane.
(2) Check the UV-Fiber-Optic Cable for any fiber breakage.
(3) Shut off operating voltage briefly and switch it back on.
(4) See beginning of test item 5.2
(5) Is the UV - test fault still there?
(6) UV - Transmitter type: TE d 07, part ID: 80567.
(7) Shut off operating voltage briefly and switch it back on.
(8) See beginning of test item 5.2
(9) Is the UV - test fault still there?
(10) PCB type: Replace FL (Ex) d 07 MCU, part ID: 80569.
(11) Shut off operating voltage briefly and switch it back on.
(12) See beginning of test item 5.2
5.3. Prior to commissioning the UV flame detector type: FL (Ex) d 07-.-FB-..
Make sure that the UV flame detector is not damaged.
Make sure that the UV flame detector is properly installed.
Make sure that no foreign particles are in the pressure-resistant interior of
the UV flame detector.
Make sure that any open drill holes or unused screwed cable glands are closed
using blind plugs certified according to Directive 94/9/EC. Do not forget the Seal
between the enclosure and the blind.
Observe the temperature resistance of the Seal between -40°C and +125°C.
Check the screwed cable glands and blind plugs for a tight fit.
Check the screwed cable glands and blind plugs for any damage.
Make sure that the fieldbus system is configured.
Make sure that the fieldbus node address is configured in the fieldbus system .
Refer to nameplate of UV flame detector
e.g. "PROFIBUS, DP slave, Address no.: 10 (Hex), 16 (Dec)“
Ensure the position that the UV flame detector has in the fieldbus system, line
detector or end detector.
See "S1" switch in the UV flame detector / factory default setting = "E"
Please set according to the position: "E" = end detector or "L" = line detector
Once the work has been completed, ensure that the UV flame detector has
been carefully closed with the enclosure cover.
In this regard, also refer to the section
"Closing / opening enclosure cover"
K2
LED
Blink