VS00E01KNXFI01010007.
DOC
Eelecta® Touch Panel 3,5 KNX – Product Handbook
40/156
Eelectron SpA, Via Magenta 77/22, I-20017 Rho (MI), Italia
+39 02.9316681 +39 02.93507688
[email protected] www.eelectron.com
VS00E01KNXFI01010007.doc
C.F. e P.IVA 11666760159
Capitale sociale: 250.000,00€ interamente versato
Tribunale di Milano 359157-8760-07
CCIAA Milano 148549
Here, the graphics have to be adjusted in advance
;IMGVAL=ampel;
5.9 1-Byte-Value-Slider
0..100%
ETS objects:
Simple element to send/receive a 1-byte value 0...255.
Use IMGSET to choose the set of images you want to use.
NOBG eliminates the button’s surface and the display is
visualized directly on the background.
Using PF, a unit of measurement can be adjusted
according to the measured value.
STEPS determines the step width which is required to get
from the minimum to the maximum (given that MIN and
MAX are set)
MIN determines lower limit.
MAX determines upper limit.
When pressing the buttons a little longer, REP sets the
interval by which the values are sent. (in milliseconds)
If "Use PIN" is selected, the default master password will
be used in case PIN is not set. Using PIN, an individual
password can be assigned.
AL/AH can only be used on alarm side. They serve as a
limit setting the temporal point from which an alarm is
detected.
Range of values
0...255
Input
Feedback
1 Byte
Output
Switching
1 Byte
Format:
W
Determines width of button's surface
IMGSET
Choosing set of images
NOBG
No button background
PF
Declaration of the unit
STEPS
Setting step width
MIN
Default setting of lower limit
MAX
Default setting of upper limit
REP
Setting repetition rate
PIN
In case "Use PIN" is selected, an
individual password can be assigned
using PIN
AL
Alarm lower limit / ONLY ON ALARM
AH
Alarm upper limit / ONLY ON ALARM
examples:
1Byte-Slider;IMGSET=light;MIN=50;MAX=80;
STEPS=15;REP=1000;
1Byte-Slider;IMGSET=volume;MIN=20;MAX=70;
STEPS=16;REP=500;
1Byte-Slider;