VS00E01KNXFI01010007.
DOC
Eelecta® Touch Panel 3,5 KNX – Product Handbook
145/156
Eelectron SpA, Via Magenta 77/22, I-20017 Rho (MI), Italia
+39 02.9316681 +39 02.93507688
[email protected] www.eelectron.com
VS00E01KNXFI01010007.doc
C.F. e P.IVA 11666760159
Capitale sociale: 250.000,00€ interamente versato
Tribunale di Milano 359157-8760-07
CCIAA Milano 148549
If set to 0, the fan outputs are set as given by the controller.
19.71. Input, Fan Speed [218]
Allows to define the value which is then available to set[1] via the object "Input, Fan Mode" as shown in the table. If this
value is changed, the corresponding outputs of the objects "Output, Fan VX" and "Output, Fan Continuous [%]" are
immediately set to the corresponding value. As usual, these values only remain active for the time set in the parameter
"Overwrite timeout [ minutes ] (Temp. Controller Settings), Page 131 “.
The new values are output immediately when they are changed. This makes it possible to see if the desired setting
is OK without having to change the object "Input, Fan Mode" after every change..
Value
,,Input, Fan Speed''
Object
,,Output. Fan Continuos
Object,,Output,Fan
V1'' V2'' V3''
0 0%
0
0
0
1
Parameter „Controller Fan Limit 1 [%]“ (Controller Page
Fan)
1 0 0
2
Parameter „Controller Fan Limit 1 [%]“ (Controller Page
Fan)
0 1 0
3
Parameter „Controller Fan Limit 1 [%]“ (Controller Page
Fan)
0 0 1
19.72. Output, Status1 [220]
Provides general room controller status information.
This is inspired by the DPT_HVACStatus, only the fourth bit differs, which is not the dew point, see table.
Bit Attributes
Description
Encoding
b0
Comfort Mode
Indicates if Comfort Mode is active or
not
1=active 0=inactive
b1
Standby Mode
Indicates if Standby Mode is active or
not
1=active 0=inactive
b2
Economy Mode
Indicates if Economy Mode is active or
not
1=active 0=inactive
b3
Frost/Heat protection Mode
Indicates if Protection Modes is active
(only Mode)
1=active 0=inactive
b4
OFF Mode
Indicates if OFF Mode is active or not
1=active 0=inactive
b5 Heating/Cooling
Indicates
if controller is heating or
cooling
1=active 0=inactive
b6
Controller Status
Indicates if one Heating or Cooling
output is not equal 0
1=active 0=inactive
b7
Frost alarm
Indicates if in Protection mode and
controller is active (controller output not
equal zero)
1=active 0=inactive