STANDARD STARTING CONDITION
• SW1 - position 1 (minimum threshold level)
• SW2 - position 1 (minimum threshold level )
• SW3 - position 4 (maximum Trasmitter power )
• JP1 - position 2-3 (optical allignment ON)
• JP2-JP3 - position 2-3 (alarm and turbulence relays NC)
• JP4 - position 1-2 (Fault relay NC)
• JP5 - position 1-2 (memory OFF)
• JP7 - not insert (alarm relay deactivated)
NOTE - the version -S detectors (RK100-BS) are not equipped with the Turbulence detection circuit. Therefore
no items related to this function are included. Keep in mind this indication while reading and using these
instructions.